UNI EN ISO 9001-2015 n° 9115.BRMO
USER MANUAL
“Aquarius Plus”
File name
Date
Page
Code
PUT9I001 PUT9I1K5
DF19009A
05/04/19
30
di
32
PUT9I002
PUT9I003
MD03006C
- All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
8 Reference standards
The Braga Moro uninterruptible power supplies have been manufactured according to the
regulations listed in the table in this paragraph and have obtained the CE mark in compliance with
European standards.
EMC standards
Safety standards
IEC62040-2
IEC62040-1
IEC61000-4-2
GB4943-5
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
9 Electrical characteristics
Model
1KVAS
1KVAH
2KVAS
2KVAH
3KVAS
3KVAH
Nominal capacity
900W/1000VA
1800W/2000VA
2700W/3000VA
Input
Input type
Single-phase + earth
Voltage range
115±5VAC-295±5VAC
Frequency range
45Hz-55Hz@50HZ/55Hz-65Hz@60HZ
Power factor
≥0.98
ECO range
Output voltage variation ± 20VAC
Range Bypass
186VAC-252VAC
Harmonic current
≤7% (100
%
nonlinear load)
Output
Output type
Single-phase + earth
Nominal voltages
208/220/230/240VAC
Power factor
0.9
Voltage accuracy
±2%
Frequency
Exit
Line mode
1) When the input frequency is within the limits, the output frequency is
the same as the input frequency.
2) When the input frequency is not within the limits, the frequency is
(50/60 ± 0.2) Hz.
Battery mode
(50/60±0.2) Hz
Crest factor
3-1
Transfer time
Network ← → battery = 0ms
Network←→ bypass =4ms
Capacity
overload
Battery mode 108%±5%<load≤150%±5%
>
30s cut off output and warn,
150%±5%<load<200%±5%
>
300ms cut off output and warn
Line mode
108%±5%<load≤150%±5%
>
30s transfer. al bypass e notice
150%±5%<load<200%±5%
>
300ms transfer. al bypass e notice