Mechanical data
Spring terminal (connector)
Unit
min.
max.
Connection cable
Stranded wire
mm
2
0.25
1.5
AWG
24
16
Stripped length
mm
10
Tab. 6-39:
Mechanical data
Electrical data (output for controlling motor holding brake [XG3.3/4])
Spring terminal (connector)
Unit
min.
max.
Output current
A
0.15
1)
1.29
Overvoltage protection continuous power
W
n.s.
1.5
Energy absorption
Ws
n.s.
3
1)
With deactivated brake current monitoring: 0 A
Tab. 6-40:
Electrical data (output for controlling motor holding brake [XG3.3/4])
Motor holding brake: Selection
Maximum current rating of XG3 outputs: 1.29 A
⇒ R
br (min)
= U
br (max)
/ 1.29 A
R
br (min)
: minimum allowed resistance of motor holding brake
U
br (max)
: maximum supply voltage of motor holding brake
If U
br (max)
= 24 V +5% = 25.2 V, then:
R
br (min)
= 19.53 Ω (applies to all operating and ambient conditions)
Motor holding brake: Notes on in‐
stallation
Make sure there is enough power supply to the motor for the motor holding
brake. Note that voltage drops on the supply line. Use connection lines with
the largest possible cross section of single strands.
Use an external contact element in accordance with the required safety cate‐
gory if you want to supply motor holding brakes with higher currents than the
current load allowed at XG3. Make sure to comply with the required minimum
current consumption of 100 mA when using an external contact element. Oth‐
erwise the brake current monitor will signal an error.
DOK-INDRV*-KCU02+KSM02-PR03-EN-P
Bosch Rexroth AG
173/337
Rexroth IndraDrive Mi Drive Systems with KCU02 KSM02, KMS02/03, KMV03, KNK03
Connection points