View
Connection
Signal name
Function
PE
Equipment grounding conductor
14
L-
Power supply, DC 750 V, 25 A
13
L+
12
0V
42 V supply, max. 15 A
11
42V
10
Ext_SI_Ch1_In (X103.1)
Ext_SI_Ch1 (X103.2)
Control signals (24 V)
9
Ext_GND_In (X103.1)
Ext_GND (X103.2)
8
Ext_SI_Ch2_In (X103.1)
Ext_SI_Ch2 (X103.2)
7
bModulbus
6
bE_Stop_In (X103.1)
bE_Stop_Out (X103.2)
5
Shield
Multi-Ethernet
4
RxD-
3
TxD-
2
TxD+
1
RxD+
Contact design
Pins on device
Tab. 6-21:
Function, pin assignment, properties
Notes on installation
●
Exclusively operate KSM02/KMS02/KMS03 at a KCU02 or KMV03.
●
Always connect the hybrid cable of KCU02 to the connection point
X103.1 of the first KSM02/KMS02 of a drive line.
●
Hybrid cables contain power lines and control lines. Always route hybrid
cables in such a way that the hybrid cables are protected against exter‐
nal damage (in accordance with EN 61800‑5‑1 and EN 61800‑5‑2).
Notes on Operation
Do not remove connectors when the component has been powered. Do not
plug in connectors when the component has been powered.
Bosch Rexroth AG
DOK-INDRV*-KCU02+KSM02-PR03-EN-P
148/337
Rexroth IndraDrive Mi Drive Systems with KCU02 KSM02, KMS02/03, KMV03, KNK03
Connection points