24
Climate Class 6100i / 6000i / 8100i / 8000i
Correct the installation of the thermistor
and the connector on IDU PWB.
Replace pipe temperature thermistor.
Check if the pipe temperature thermistor is
firmly installed and connected with IDU PWB
properly.
Check if the lead wire of the pipe temperature
thermistor is broken or the sheath of it is
damaged leading to short circuit.
Pipe temperature thermistor
Check if the resistance of the pipe temperature
thermistor is correct. (Refer to THERMISTOR
TEMPERATURE CHARACTERISTICS)