4-9
Climate Class 6100i / 6000i / 8100i / 8000i
3.
Inverter electrolytic capacitor (C5,C6:For CLC6101i 50/65 HE/ CLC6001i 25/35 E models;C8,C9:For CLC8101i 65
HE/ CLC8001i 25 /35 models) check method
Turn off the power, let the inverter electrolytic capacitor (C5,C6:For CLC6101i 50/65 HE/ CLC6001i 25/35 E models;C8,C9:For CLC8101i 65 HE/ CL-
C8001i 25 /35 models) discharge completely, and remove the capacitor from the control printed circuit board (PWB). First, check the case for cracks,
deformation and other damages. Then, using a needle-type tester, check continuity.
Determination of normal condition
The tester needle should move on the scale and slowly returns to the original position. The tester needle should move
in the same way when polarities are reversed. (When measurement is taken with the polarities reversed, the tester
needle exceeds the scale range. Therefore, let the capacitor discharge before measurement.)
4.IPM check method
Turn off the power, let the large capacity electrolytic capacitor (C5,C6:For CLC6101i 50/65 HE/ CLC6001i 25/35 E models;C8,C9:For CLC8101i 65 HE/
CLC8001i 25 /35 models) discharge completely, and dismount the IPM. Then, using a tester, check leak current between C and E.
When using a digital tester, the (+) and (-) tester lead wires in the table must be reversed.
Values in ( ) are for digital tester.
Needle-type tester
Normal resistance value
(-)
(+)
P
N
∞
(several M
Ω
)
U
V
W
Needle-type tester
Normal resistance value
(-)
(+)
U
N
∞
(several M
Ω
)
V
W
5.DC Over Current Error ( 6-0 error)
* 1
Check the connection of compressor lead wire on PWB.
TU : RED
TV : WHITE
TW : ORANGE
* 2
Refer to "IPM CHECK METHOD".
* 3
Check the connection of compressor terminal marking.
Refer to " DISASSEMBLING PROCEDURE OUTDOOR UNIT".
* 4
Check to make sure thermistors are installed in correct portions.
Refer to "THERMISTOR TEMPERATURE CHARACTERISTICS".
Yes
No
Yes
No
Yes
No
Yes
* 1
No
abnormal
normal
abnormal
* 2
abnormal
normal
normal
* 3
Yes
abnormal
No
normal
Cooling mode
Heating mode
*4
*4
abnormal
abnormal
abnormal
abnormal
No
normal
normal
normal
normal
START
Replace PWB.
Modify compressor terminal
marking.
Clean indoor heat
exchanger.
Fix IPM with screws securely.
Modify or replace
termistor.
Are valves (2-way
and 3-way) close?
Does compressor
rotate?
Check IPM
lead wire.(UVW)
Check IPM
short circuit.
Check compressor
terminal.
Does compressor rotate?
Does
compressor rotate
more than 30 seconds?
Is IPM floating
from the heat sink?
Check the
AC power supply
voltage when compressor rotate.
(rated voltage±10%)
Cooling mode?
Check indoor
exchanger termistor and
discharge thermistor.
Check outdoor
exchanger termistor and
discharge thermistor.
Check indoor
heat exchanger.
Check outdoor
heat exchanger.
6-0 error memory is recorded.
Check the refrigerant amount.
Check the discharge pressure.
Check the installation condition.
Replace PWB
Replace Compressor
Fully open stop valves
Modify the connection of
compressor lead wire on PWB.
Connect stable power supply.
Clean indoor heat exchanger.
Modify or replace termistor.
Summary of Contents for CLC6001i 25 E
Page 69: ...2 Climate Class 6100i 6000i 8100i 8000i 6 1 6 3 6 4 6 2 ...
Page 77: ...10 Climate Class 6100i 6000i 8100i 8000i 6 1 6 3 6 4 6 2 ...
Page 87: ...20 Climate Class 6100i 6000i 8100i 8000i 7 28 Reverse Value Ass y ...
Page 88: ...21 Climate Class 6100i 6000i 8100i 8000i Expansion Value Ass y ...