The lead wire sheath of the ODU thermistor has been damaged due to edge or long-time
friction by vibration, and the wire toches the pipe, etc.
Check if the resistance of each ODU thermistor is
correct as shown in graph below.
(First remove the connector from the PWB, and
then measure the resistance.)