Project Configurator
3–18
1070 072 262-101 (01.09) GB
D
In case of loading process for module: select system component,
Rack_ID and Rack_Slot_ID
D
In case of loading process for selected elements: mark the component(s)
(Rack_ID, Rack_Slot_ID) the loading process is performed for in the
main window of the project configurator.
Mark
L
Load current configuration via symbol.
3.1.7
Unload Configuration
The configuration can be read out from a controllers group of CL550 system
modules located in a logical network. Via ”broadcast”, the IP addresses, the
configuration file and all Ethernet parameters as well as the status of each
responding system module are read out.
L
Start unloading via menu CONFIGURATION
"
UNLOAD
L
Enter name of the configuration
file in the dialog box. A configur-
ation file is overwritten or a new
configuration file is created in
accordance with the entered file
names.
L
Unload configuration via symbol.
.
It is not possible to check completeness, because via ”broadcast” only
the system modules in operation and located in the same subnetwork
will respond.