If the device fails to read a code of the electronic key within 10 seconds, it automatically exits from the
Master Key Programming mode. When exiting the Master Key Programming Mode, the device plays
the final part of the Programming melody.
The Master Key can be used to switch the Signal-10 device to the User Key Programming Mode to
program User keys with the status similar by default to the status of this Master Key (arm-
ing/disarming all the 10 alarm loops of the device is enabled).
Programming of User Keys by Hardware
In order to switch the device to the User Key Programming mode, touch the reader with a Master key.
If the Master key is successfully read and perceived, the device activates the programming mode and
plays a melody while READY LED and the reader LED start blinking.
The following functions are available in this mode:
−
Registering of new User keys
−
Changing privileges of already existing User keys
The Signal-10 device exits from the User Key Programming mode:
−
When the Master Key is presented to the device reader once again
−
After 30 seconds time out since the last key programming or status changing
−
After 10 seconds time out since entered the User Key Programming mode if neither key is
presented to the reader nor key status is changed
When the device exits from the User Key Programming mode, a melody sounds.
Each User key can be configured to arm/disarm an arbitrary group of device alarm loops. The follow-
ing rights to control each alarm loop of this group can be assigned to the User key:
−
arm/disarm
−
arm only
−
disarm only
If the User key has no control rights assigned to a specific alarm loop, this loop is not included to the
selected group.
A combination of access rights assigned to the key for all the alarm loops within the selected group is
called Key Status. When the device switches to the User Key Programming mode, a current status of
a User key inherits from the status of the presented Master Key (by default). In the User Key Pro-
gramming mode the current status of the presented User key is displayed by the device LEDs 1 – 10
(see Table 12).
Summary of Contents for Signal-10
Page 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Page 5: ...Signal 10 General 5 www bolid com GENERAL ...
Page 8: ...Orion ISS www bolid com 8 ...
Page 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Page 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Page 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Page 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Page 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Page 69: ...Signal 10 Installation 69 www bolid com ...
Page 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Page 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Page 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Page 96: ......