NOTE:
No threshold addressable detectors or call points with the same own address can be
included into the same fire loop of the Type 14
The Signal-10 recognizes the following messages/conditions responded by addressable devices:
Norm
Dusty, Service Required
Trouble
Fire
Manual Fire Alarm
Test
Isolated
A current condition of an alarm loop of the Type 14 is formed as a generalized condition of those ad-
dressable zones which are involved into this loop and matched with this loop by the given Related Ad-
dressable Detectors setting (see Alarm Loop Configuration Parameters section of this Manual). The
generalized condition of a loop of the Type 14 is defined as the most priority condition of all the ad-
dressable zones.
Following are all possible generalized conditions of a threshold addressable loop in the order of priority:
Fire Alarm
Two or more loop addressable zones have the Fire Alarm sta-
tus, or the Alarm Delay given for this loop has been expired
Fire Prealarm
There is at least one addressable zone in the Fire Alarm status
Trouble
There is an addressable zone with the Trouble status, and there
is no zone with the Fire Alarm status
Isolated
There is an isolated addressable zone in the loop, while there
are no zones with Fire Alarm or Trouble statuses
Fire Signal
There is an addressable zone with Test status and there are no
zones with Isolated, Trouble, or Fire Prealarm, or Fire Alarm
statuses
Arming Failed
At the moment of arming, one of the addressable zones of the
loop has a not Norm status, no other zones having more priority
statuses (said above)
Arming Delay
The transient status when after an attempt to arm an addressa-
ble zone the response from the addressable detector is waiting
for, and there are no zones with more priority statuses (said
above)
Summary of Contents for Signal-10
Page 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Page 5: ...Signal 10 General 5 www bolid com GENERAL ...
Page 8: ...Orion ISS www bolid com 8 ...
Page 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Page 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Page 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Page 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Page 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Page 69: ...Signal 10 Installation 69 www bolid com ...
Page 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Page 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Page 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Page 96: ......