Orion ISS
www.bolid.com
80
PROGRAMMING OUTPUTS
To program the Signal-10 relay outputs, use Outputs Tab of the UProg Configuration Tool (see Fig-
ure 15).
If one of the device relays is to be centrally-controlled by network controller commands than this relay
must not be related with any device alarm loop (the relative Relay…Control parameter must be set off
for all the device alarm loops
see above).
If, otherwise, a relay is to be controlled locally depending on the device alarm loop statuses, the relay
must be related to the relevant alarm loops via the relative Relay…Control parameter. Moreover, a
relay activation delay can be specified at the Alarm Loops tab
see the previous section.
NOTE:
If a relay is assigned to an alarm loop (loops) then control commands of a network con-
troller via RS-485 highway will be ignored. Local relay control is more priority than cen-
tralized one.
Figure 15. Signal-10 Relay Outputs Programming
Summary of Contents for Signal-10
Page 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Page 5: ...Signal 10 General 5 www bolid com GENERAL ...
Page 8: ...Orion ISS www bolid com 8 ...
Page 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Page 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Page 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Page 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Page 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Page 69: ...Signal 10 Installation 69 www bolid com ...
Page 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Page 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Page 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Page 96: ......