Orion ISS
www.bolid.com
50
Table 7. Programmable Auxiliary Loops Available Statuses
Status
Code
Status
Status
Code
Status
1
AC Power Restored
77
Too Low Level
2
AC Power Failed
78
Normal Temperature
3
Intrusion Alarm
82
Heat Sensor Failed
17
Arming Failed
109
Disarmed
24
Armed
118
Entrance Alarm
35
Auxiliary Zone Restored
130
Pump On
36
Auxiliary Zone Alarm
131
Pump Off
37
Fire Alarm
149
Tamper Alarm
38
Auxiliary Zone Alarm-2
152
Tamper Restored
39
Fire Equipment Restored
198
Power Failed
41
Fire Equipment Trouble
199
Power Restored
44
Fire Prealarm
200
Battery Restored
45
Loop Open Failure
202
Battery Failed
58
Panic Alarm
204
Service Required
71
Low Level
206
Low Temperature
72
Normal Level
214
Loop Short Failure
74
High Level
216
Fire Signal
75
Too High Level
220
Gas Press Signal
76
High Temperature
223
Patrol Check
While programming resistance thresholds for statuses of an alarm loop of the Type 12, it needs to know
strictly the resistance range for each of the loop status. As it is quite a difficult task, the actual alarm
loop resistances can be approximately calculated based on resistance values expressed in ACD units
and measured by the Signal-10 device using the formula:
1
281
loop
−
=
ADC
R
, [K
Ω
],
where R
loop
is the actual resistance value of an alarm loop and
ADC is the ADC-value of the resistance measured by the Signal-10 device.
This formula enables adequately calculating resistance values of the loop ranged from 0.1 K
Ω
to
50 K
Ω
. Reading the ADC values is provided either by S2000/S2000M console tools or by UProg Con-
figuration Tool while programming the loop (see Figure 13, the page 76 of this Manual).
Summary of Contents for Signal-10
Page 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Page 5: ...Signal 10 General 5 www bolid com GENERAL ...
Page 8: ...Orion ISS www bolid com 8 ...
Page 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Page 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Page 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Page 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Page 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Page 69: ...Signal 10 Installation 69 www bolid com ...
Page 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Page 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Page 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Page 96: ......