![bolid Signal-10 User Manual Download Page 78](http://html.mh-extra.com/html/bolid/signal-10/signal-10_user-manual_2785090078.webp)
Orion ISS
www.bolid.com
78
for example, to unset power of four-wire detectors (by means of the Switch On For a Time Before
Arming executive program), the alarm loop MUST be programmed with a non-zero Arming Delay val-
ue.
Loop Analysis Delay
The Loop Analysis Delay for an alarm loop of any type defines the duration of a pause between start-
ing powering the loop and analyzing its conditions. This delay enables including into alarm loops the
detectors with high worm-up times (settling times). For such the detectors the Loop Analysis Delay
must be set to a value slightly exceeding the maximum readiness time.
The minimum hardware delay is 1 s (the default value). This value can be increased up to 63 s.
Activation Delay for Relay 1 - Activation Delay for Relay 4
If changing the statuses of the given alarm loop must cause one of the device relay outputs to be acti-
vated (see Relay … Control parameters below), the relay can be activated not immediately but after a
time given by the Activation Delay for Relay … parameter (from 0 s to 255 s).
NOTE:
If the following executive programs are given for a relay (see Table 5):
9 (Lamp),
10 (Alarm Output 1),
13 (Fire Output),
14 (Trouble Output),
15 (Fire Lamp), and
16 (Alarm Output 2),
then this parameter setting is ignored, the output being activated immediately after
changing a status of the programmed alarm loop.
By default, activation delays are equal to zeros for all the alarm loops.
Never Disarmed
This parameter is set off by default and should be set on when disarming of an alarm loop (either ac-
cidental or intentional) is inadmissible.
Auto Rearming After Failing
By default, an alarm loop is automatically armed when it is in the Arming Failed mode and its re-
sistance keeps the normal value for more than 3 s. To prohibit an alarm loop to be automatically
armed, turn this parameter off for this loop.
Auto Arming After Alarm
If this parameter is turned off for an alarm loop, the alarm loop automatically switches from the Intru-
sion Alarm, Panic Alarm, or Fire Alarm status to the Armed status if loop resistance has been within
Summary of Contents for Signal-10
Page 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Page 5: ...Signal 10 General 5 www bolid com GENERAL ...
Page 8: ...Orion ISS www bolid com 8 ...
Page 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Page 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Page 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Page 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Page 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Page 69: ...Signal 10 Installation 69 www bolid com ...
Page 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Page 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Page 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Page 96: ......