Signal-10
Operation Principles
15
www.bolid.com
Table 1. Alarm Loops Configuration Parameters
Parameter
Description
Value Range
Loop Type
Defines
the tactics the alarm loop to be monitored for,
the kind of detectors to be included into the
alarm loop, and
statuses to be assigned to the alarm loop
1 – Smoke Two Threshold
2 – Fire Combined
(Smoke + Heat)
Single Threshold
3 –Heat Two Threshold
4 – Intrusion
5 – Intrusion With Tamper
Monitoring
6 – Auxiliary
7 – Entrance
11 – Panic
12 – Programmable
Auxiliary
14 – Fire Threshold
Addressable
Alarm Delay
The delay for switching between
Entrance Alarm and Intrusion Alarm statuses, or
Fire Prealarm and Fire Alarm statuses
From 1 to 254 s,
the ‘0’ value means ‘with-
out a delay’
the ‘255’ value means
‘infinite delay’
Arming Delay
The delay between receiving the arming com-
mand and switching the loop to Armed mode
From 0 to 255 s
Auto Rearming
After Failing
Automatic switching from Arming Failed status
to Armed status when the alarm loop having
restored
On / Off
Loop Analysis Delay
The time interval required for transient process-
es to be completed within the alarm loop after
powers resets. During this time the status of the
alarm loop will not be analyzed
From 1 to 63 s
Relay 1 (‘Alarm 1’)
Activation Delay
The delay in seconds between having the relat-
ed alarm loop (loops) broken and activating the
relay
From 0 to 255 s
Relay 2 (‘Alarm 2’)
Activation Delay
Relay 3 (‘Siren’)
Activation Delay
Relay 4 (‘Lamp’)
Activation Delay
Never Disarm
The alarm loop cannot be disarmed by any way
On / Off
Auto Arming
After Alarm
Automatic switching from the Intrusion Alarm,
Panic Alarm, or Fire Alarm status to the Arming
Delay status when the alarm loop has been
restored
On / Off
Disarmed Loop
Monitoring
The directive to transmit over RS-485 interface
messages about altering conditions (Norm/No
Norm) of the disarmed loop
On / Off
Summary of Contents for Signal-10
Page 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Page 5: ...Signal 10 General 5 www bolid com GENERAL ...
Page 8: ...Orion ISS www bolid com 8 ...
Page 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Page 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Page 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Page 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Page 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Page 69: ...Signal 10 Installation 69 www bolid com ...
Page 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Page 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Page 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Page 96: ......