the normal range. It is advisable to set this parameter on for such the alarm loops which involve detec-
tors producing high voltage ripples in the alarm loop.
The Related Addressable Detectors parameters relates an alarm loop of the Type 14 (the threshold
addressable alarm loop) with the addresses of the already installed into the loop addressable detectors
or call points – see Fire Threshold Addressable Alarm Loop (Type 14) section of this Manual. If the ad-
dressable zone of an addressable detector or call point is not related to an alarm loop, this zone doesn’t
take part in generating of a generalized loop and is not affected by loop arming/disarming commands.
Alarm Loop Types
The main alarm loop configuration parameter which defines the way the controller considers the condi-
tions of the alarm loop is the Loop Type. The Signal-10 supports 10 different types of alarm loops.
Table 2 shows how the current resistance values of alarm loops are considered by the Signal-10 device
to be different loop statuses depending on the current type of the alarm loop.
Table 2. Alarm Loop Resistance Values for Different Loop Statuses
Loop Type
Alarm Loop Conditions and Statuses
Type 1
Smoke
Two Threshold
Short
Circuit
Fire Alarm
(two or more
smoke detectors
have actuated)
Fire Prealarm
(a smoke
detector
has actuated)
Norm
Open Circuit
Less than
100
Ω
From 150
Ω
to
1.56
*
k
Ω
From 1.1
*
k
Ω
to
1.8 k
Ω
From 2.2 to
5.4 k
Ω
More than 6.6 k
Ω
* Depends on the loop load cur-
rent
Type 2
Fire
Combined
Single
Threshold
Short
Circuit
Fire Prealarm/
Fire Alarm
(a smoke
detector
has actuated)
Norm
Fire Prealarm/
Fire Alarm
(a heat detector
has actuated)
Open Circuit
Less than
100
Ω
From 150
Ω
to
1.8
*
k
Ω
From 2.2 to
5.4 k
Ω
From 6.6 to 14.4
k
Ω
More than 16 k
Ω
Type 3
Heat
Two Threshold
Short
Circuit
Norm
Fire Prealarm
(a heat detector
has actuated)
Fire Alarm
(two or more
heat detectors
have actuated)
Open Circuit
Less than
1.8 k
Ω
From 2.2 to
5.4 k
Ω
From 6.6 to
11 k
Ω
From 12.5 to
22.5 k
Ω
More than 25 k
Ω
Type 4
Intrusion
Norm
Intrusion Alarm
From 2.2 to 10 k
Ω
Less than 1.8 k
Ω
, or more than 12 k
Ω
, or has jumped
by more than 10 %
Summary of Contents for Signal-10
Page 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Page 5: ...Signal 10 General 5 www bolid com GENERAL ...
Page 8: ...Orion ISS www bolid com 8 ...
Page 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Page 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Page 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Page 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Page 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Page 69: ...Signal 10 Installation 69 www bolid com ...
Page 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Page 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Page 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Page 96: ......