AUXILIARY ALARMS
The Signal-10 device enables monitoring and transmitting to an Orion network controller the conditions
of various technological circuits being not directly related to fire and intrusion alarms. Such the circuits
involve contacts of devices blocking automated fire–fighting systems, mass sensors, press sensors,
flow sensors, throttle valves, liquid level controls and so on.
For these purposes the loops of Type 6 (Auxiliary) and Type 12 (Programmable Auxiliary) are used.
Loops of these types can be neither armed nor disarmed: they are always monitored by the device,
breaking of these loops (that is, Auxiliary Alarms) being always indicated by the Signal-10 device and
transmitted to the network controller.
Auxiliary loops of the Type 6 are considered to be in one of two available statuses, namely the Auxil-
iary Zone Alarm and Auxiliary Zone Restored ones. In such a case, if an alarm loop of the Type 6 is
matched with any relay output of the Signal-10 (the relevant Relay … Control parameter is on for this
loop) breaking of the loop will block activation of the relay controlled in accordance with a given pro-
gram.
This type of alarm loops is suitable, for example, to block automatic start of a fire-fighting system in the
case when a door to the premises is opened.
An alarm loop of the Type 6 switches from the Auxiliary Zone Restored status to the Auxiliary Zone
Alarm status if the alarm loop has held broken for at least 300 ms.
Recovering of the broken alarm loop of the Type 6 (that is, switching from the Auxiliary Zone Alarm to
the Auxiliary Zone Restored status) is implemented automatically if the resistance of this loop has come
to the normal range and is held normal for the time interval equal to Arming Delay parameter pro-
grammed for this loop.
Breaking of an alarm loop of the Type 6 causes blocking the relay related with this loop and controlled
by the following programs:
−
#1…#8 (general purpose programs)
−
#11 (ASPT)
−
#12 (Siren)
−
#33 (ASPT-1)
−
#34 (ASPT-A)
−
#35 (ASPT-A1)
Blocking of a relay upon breaking of a loop of the Type 6 implies that:
−
The relay is not activated if the loop has already been broken
−
The relay is returned to an initial condition of the given executive program if the relay was
being controlled when the loop has been broken.
Summary of Contents for Signal-10
Page 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Page 5: ...Signal 10 General 5 www bolid com GENERAL ...
Page 8: ...Orion ISS www bolid com 8 ...
Page 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Page 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Page 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Page 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Page 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Page 69: ...Signal 10 Installation 69 www bolid com ...
Page 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Page 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Page 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Page 96: ......