6.11. SERVICE SETTINGS
When using the controller service settings of the pellet burner, the access is allowed by a
password. The password is reactivated after exiting the menu, if within 15 seconds no button
is pressed.
The service seatings procedures of the pellet burner are password protected
and can be applied only by trained service specialists, disposing of
additional information.
In the transitional seasons it is recommended to operate the boiler
ONLY
with
wood pellets, in order to avoid the danger of overheating when the used fuel is
in the form of wood or wood chips.
6.11.1. IGNITION SETTINGS
Table 11. Ignition settings of pellet burner
Name
Indication
Limit
Factory
settings
Bisolid
Automat 25
Factory
settings
Bisolid
Automat 35
Factory
settings
Bisolid
Automat 45
Factory
settings
Bisolid
Automat 60
Time for loading
Load
2 – 480 s
20 s
20 s
20 s
20 s
Time for blowing
Blowing
0 – 10 m
2 m
2 m
2 m
2 m
Time for flame
occurrence
Fire time
1 – 15 m
3 m
3 m
3 m
3 m
Time for preheating
Preheat
0 – 180 s
20 s
20 s
20 s
20 s
Fan for fresh air
Fan1
20 – 100%
70%
70%
70%
70%
Time for inflame
Inflame
60 – 600 s
120 s
120 s
120 s
120 s
Water temperature
T set
0 - 90
о
С
70
о
С
70
о
С
70
о
С
70
о
С
Zone regulation of T
к
Zone reg
0 - 30
о
С
5
о
С
5
о
С
5
о
С
5
о
С
Flue gases temperature
Tfg set
100- 400
о
С
200
о
С
200
о
С
200
о
С
280
о
С
Zone regulation of Tfg
Zone reg
Tfg
0 – 30 °C
10
о
С
10
о
С
10
о
С
10
о
С
Tubus operation
Tubus
work
0 – 100%
0%
0%
0%
0%
Ignition settings
Load 90 s
Blowing
2 m
Fire time
8 m
Preheat
100 s
Fan1
48 %
Inflame
120 s
Ignition settings
Т
set
70 °C
Zone reg.
10 °C
Tfg set
160 °C
Zone_reg Tfg
20 °C
Tubus work
0 %
EXIT