INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Bisolid Automat OM-BAV04/10/2017/EN
15
Figure 5. Outer view of hot water boiler series Bisolid Automat
Technical data of hot water boiler series Bisolid Automat burning preferred fuel (wood pellets)
are presented in Tables 4.
Table 4. Hot water boiler series Bisolid Automat technical data in operation with
preferred fuel (wood pellets)
Parameter
Dimension
Value
Boiler model
-
Bisolid
Automat 25
Bisolid
Automat 35
Bisolid
Automat 45
Bisolid
Automat 60
Preffered fuel
-
Wood pellets
Nominal heat output
kW
18
26
30
40
Operating pressure
bar
2.0
2.0
2.0
2.0
Operating draft
Ра
> 20
> 20
> 30
> 37
Efficiency
%
87
90
86
80
Energy efficiency class
according to regulation (
Е
U)
2015/1187
-
Boiler class according to
standard EN 303-5:2012
-
5
Flue gas temperature at rated
power
о
С
180
170
194
260
Boiler water volume
l
70
100
105
130
Hopper volume
l
79
105
119
180
Boiler weight including the
pellet burner
kg
261
311
324
465
Power supply
-
230VAC, 50Hz
Electrical protection
-
IP 20
The technical parameters of hot water solid fuel boilers series Bisolid Automat according to the
delegated Regulation (EU) 2015/1187 are presented in Table 5.