INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Bisolid Automat OM-BAV05/02/2018/EN
32
4. OPERATION INSTRUCTIONS
4.1. OPERATION OF BOILER BISOLD AUTOMAT
The boiler should be maintained only by adult persons, preliminary acquainted with the boiler
operation and maintenance. The boiler service and maintenance personnel should strictly
comply with the manual and should only commission the boiler, adjust the temperature of the
thermal power regulator, decommission the boiler and conduct ongoing monitoring of ts
operation. After commissioning the boiler, the service technician should acquaint the user with
the boiler operation and maintenance. Unattended children are not allowed near the boiler.
Any activity on the construction of the boiler, which might endanger the life and health of the
maintenance personnel or of persons present in the boiler room, is strictly forbidden.
The boiler should be operated at a maximum water temperature of 90
o
C and is subject to
ongoing control. Use of flammable liquids for easy firing as well as any activities related to
increasing boiler rated power (overloading) are strictly forbidden. Positioning of flammable
objects on top or near the boiler is not allowed. The ash should be taken out in fireproof
container with cover.
In case of danger from penetration of flammable vapors or gases in the boiler
room or any activities that might lead to fire or explosion (bonding flooring,
varnishing with flammable paints or others), the boiler should be
decommissioned before starting any of these activities.
4.2. SAFETY OPERATION OF THE BOILER
Relevant safety instructions should be observed when operating the boiler. Bisolid Automat
Boiler should not be used for any other purposes except for those indicated in this manual.
When operating the boiler Bisolid Automat, always a heating circuit has to be
included in which the water is circulated. If the heating radiators are equipped
with thermostatic valves (or other control components), which close the
circulations water flow. As a result of this process it is possible that the
generated heat energy, from the fuel final combustion, can’t be adopted by the
heating system (can’t be unloaded) and to lead to overheating of the appliance.
Therefore in case the boiler Bisolid Automat is operated in heating systems with
radiator regulation valves, it is necessary not to completely close the radiator
valves, but to adjust them to minimum value. Also one of the radiators should
not be equipped with regulation valve, in order to ensure adoption of the heat
energy generated during the process of final combustion.
Boiler surface should be cleaned only with standard inflammable cleaners. Positioning of
objects made of flammable materials near the boiler at an unsafe distance is not allowed.
It is not allowed to store flammable materials (wood, paper, oil, diesel oil, petrol and other
readily flammable materials) in the boiler room. The minimum allowed distance between
boiler
’
s outer parts and the flue pipe and any average or not readily flammable materials
(which dye out after firing without any additional heat energy), should be not less than 100
mm.
The allowed distance from readily flammable materials (which continue to burn after removal
of the firing source) should be minimum 200 mm.