INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Bisolid Automat OM-BAV05/02/2018/EN
46
When the room thermo-regulator is switched on or off and there is an optimization (5-60
minutes), the setup values of the heating water are:
At switching on
–
an increase starts and the maximum setup values are reached at the
end of the optimization time, only if there has been no switching off during that period.
At switching off
–
a decrease of the setup values starts, and the minimum setup values
are reached at the end of the optimization period, only if there has been no switching
on during that period.
6.8. TEMPERATURE RESTRICTIONS AND PROTECTIONS
When operating tube pellet burner Bisolid GP xx R tsc it is necessary to consider the following
temperature restrictions and protections:
Minimum setup values of the inlet water temperature.
Maximum setup values of the inlet water temperature.
Water freezing protection.
Boiler overheating and
„
back-fire
”
protection.
Circulation pump blocking protection.
Maximum setup values of the temperature of the exhaust gases for main inlet fuel and
for other suitable fuel.
Freezing protection - starts the burner at temperatures below
5 °
С
.
Boiler overheating and
„
back-fire
”
protection
–
blocking thermostat inlet,
when opening the signal contact, the burner stops.
Protection from blocking the circulation pump
–
drives/rotates the pump for
5 minutes, in case it has not been operating for 24 hours.
The maximum and the minimum setup values of the heating water temperature delimit the
water supplied to the premises. (See Section Programming
“
Service Settings").
6.9. PELLET BURNER FRONT PANEL
Figure 17 shows the front panel - intuitive LCD display of a tube pellet burner Bisolid GP xx R
tsc. Parameters indications on pellet burner display are given in Figure 18.
Figure 17. Front panel of tube pellet burner Bisolid GP xx R tsc
1. Front panel indication – intuitive LCD display.
2. Changing button
“Forward”
/ or manually switching on/off the pellets transport auger
(if holded for 5 sec. together with additionally known conditions described below).
2
3
4
5
1