Example:
Desired temperature value: 40 °C, desired safety controller value: 45 °C.
Possible settings for this example:
Temperature set point
Safety controller mode
Safety controller set-point
40 °C
Limit (absolute)
45 °C
Offset (relative)
5 °C
15.3.2 Setting the safety controller
Press the
Setpoint setting
icon to access the “Setpoint” setting menu from Normal display.
“Setpoints” menu.
Select the field “Safety controller” to access the set-
tings.
•
In the field “Mode” select the desired setting
“Limit” or “Offset”.
•
Select the corresponding field “Limit”
or
“Offset” according to the selected mode and enter the desired
safety controller setpoint. Confirm entry with
Confirm
icon.
Regularly check the safety controller setting for set-point type “Limit” or “Offset”
•
in Fixed value operating mode according to the entered set-point temperature value
•
in program mode according to the highest temperature value of the selected temperature
program
Set the safety controller set-point by approx. 2 °C to 5 °C above the desired temperature set-
point.
After completing the settings, press the
Confirm
icon to take over the entries and exit the menu,
or
press
the
Close
icon to exit the menu without taking over the entries.
Summary of Contents for 9020-0402
Page 159: ...MK LIT E5 01 2021 page 159 172 30 7 Dimensions LIT MK 240 dimensions mm...
Page 160: ...MK LIT E5 01 2021 page 160 172 LIT MK 720 dimensions mm...
Page 162: ...MK LIT E5 01 2021 page 162 172...
Page 163: ...MK LIT E5 01 2021 page 163 172...
Page 165: ...MK LIT E5 01 2021 page 165 172...
Page 166: ...MK LIT E5 01 2021 page 166 172 31 3 Safety concept certificate from T V S d...
Page 173: ......