VISTA SW 260 SXL / VISTA SW 260 MXL
INSTALLATION MANUAL
PARAMETER
DEFINITION
MIN
MAX
DEFAULT
PERSONAL
DESCRIPTION
13
Mode
Single/Dual
0
2
0
0 = Single
1 = Dual Master
2 = Dual Slave
14
Electric lock activation
according to the selected logic
0
3
3
0 = never
1 = One EXT Radar
2 = Two Radars, One INT Radar
3 = Always (1 INT Radar, 1 EXT Radar, 2 Radars)
15
AUX-IN 1 auxiliary input
confi guration
0
16
0
0= Disabled People opening
1= Emergency opening
2 = Door interlock with priority
3 = Door interlock without priority
4 = Lock Release feedback
5 = Lock Release command
6 = Single Command with Master/Slave operating mode
7 = Stand by mode activation
8 = It resets the door after the Stand by
9 = Step-by-Step (1 pulse opens, 1 pulse closes)
10 = Fire Emergency opening
11 = Manual logic setting
12 = Closed Stop logic setting
13 = Disabled People opening in manual mode
14 = Step-by-Step with automatic closing-back (pause time expressed in minutes rather than in
seconds
15 = Closed door contact
16 = Full or Partial Open selection
16
AUX-IN 2 auxiliary input
confi guration
0
16
1
0= Disabled People opening
1= Emergency opening
2 = Door interlock with priority
3 = Door interlock without priority
4 = Lock Release feedback
5 = Lock Release command
6 = Single Command with Master/Slave operating mode
7 = Stand by mode activation
8 = It resets the door after the Stand by
9 = Step-by-Step (1 pulse opens, 1 pulse closes)
10 = Fire Emergency opening
11 = Manual logic setting
12 = Closed Stop logic setting
13 = Disabled People opening in manual mode
14 = Step-by-Step with automatic closing-back (pause time expressed in minutes rather than in
seconds
15 = Closed door contact
16 = Full or Partial Open selection
17
AUX-OUT auxiliary output
confi guration
0
5
0
0 = Interlock
1 = Door open state
2 = Door closed state
3 = Fault
4 = Lock command repetition
5 = Door in motion
18
Safety sensor confi guration
0
3
0
0 = Monitoring disabled
1 = Monitoring enabled for closing sensor
2 = Monitoring enabled for opening sensor
3 = Monitoring enabled for opening and closing sensor
19
Multi Master address
0
15
0
0= No Multi-Master management
0 ÷ 15= Univocal address for Multi-Master connections
20
Opening safety by-pass [%]
0
40
0
Opening safety by-pass angle, percentage of the total stroke.
21
Master/Slave opening off set [s]
0
100
0
Slave motor delay time during opening with respect to the master motor. 100ms step