Err
or
code
Diagnostic code
Meaning for the LMV37.4... system
Remedy
51
#
Internal error
Make a reset; if error occurs repeatedly, replace the unit
55
#
Internal error
Make a reset; if error occurs repeatedly, replace the unit
56
#
Internal error
Make a reset; if error occurs repeatedly, replace the unit
57
#
Internal error
Make a reset; if error occurs repeatedly, replace the unit
58
#
Internal error
Make a reset; if error occurs repeatedly, replace the unit
60
0
Internal error: No valid output source
Make a reset; if error occurs repeatedly, replace the unit
65
#
Internal error
Make a reset; if error occurs repeatedly, replace the unit
66
#
Internal error
Make a reset; if error occurs repeatedly, replace the unit
67
#
Internal error
Make a reset; if error occurs repeatedly, replace the unit
70
#
Error air-fuel ratio control: Position calculation modulating
23
Output invalid
No valid output
26
Curvepoints undefined
Adjust the curvepoints for all actuators
71
#
Special position undefined
0
Home position
Parameterize the home position for all actuators used
1
Prepurge position
Parameterize the prepurge position for all actuators used
2
Postpurge position
Parameterize the postpurge position for all actuators used
3
Ignition position
Parameterize the ignition position for all actuators used
72
#
Internal error air-fuel ratio control
Make a reset; if error occurs repeatedly, replace the unit
73
#
Internal error air-fuel control: Position calculation multistep
23
Output invalid
No valid output
26
Curvepoints undefined
Adjust the curvepoints for all actuators
75
#
Internal error air-fuel ratio control: Data clocking check
1
Current output different
2
Target output different
4
Target positions different
16
Different positions reached
Can be caused by different standardized speeds (e.g. after resto
re of data set)
when the VSD is activated
standardize again and check adjustment of the
air-fuel ratio control system
76
#
Internal error air-fuel ratio control
Make a reset; if error occurs repeatedly, replace the unit
Summary of Contents for BG 550i M
Page 31: ...32 Bentone I I J G G G H 172 615 56 2018 08 10 ...
Page 63: ...63 Bentone 13 2 Wiring diagram 172 615 84 1 2021 05 19 2 ...
Page 64: ...64 Bentone 13 3 Wiring diagram RWF 50 3 172 615 84 1 2021 05 19 3 ...
Page 65: ...65 Bentone 13 4 Wiring diagram RWF 50 2 172 615 84 1 2021 05 19 4 ...
Page 66: ...66 Bentone 13 5 Wiring diagram Jumo 316 172 615 84 1 2021 05 19 5 ...
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com ...