102
Bentone
P
V
h
min
s
%
Bi
ld
9
4
/0
7
0
7
When symbol
or
is no longer highlighted, you can press
ESC
a
second time.
ESC
-
+
P
V
h
min
s
%
Bi
ld
1
2
8
/0
7
0
7
The warm settings for air-fuel ratio control by the LMV37.4... are now completed.
P
V
h
min
s
%
Bi
ld
1
2
7
/0
7
0
7
The minimum capacity is displayed.
If the display shows - - - -, the minimum
capacity has not yet been entered.
The system can be run down to 20%.
You can press
/reset
to go to editing mode,
enabling you to change the minimum capacity.
Adjust the setting downwards or upwards using the buttons
-
+
Press
/reset
to save the setting.
Press
ESC
-
+
to return to parameter level.
ESC
-
+
Completing
parameterization of the
curve
-
Back to the previous
parameter