![Bentone BG 550i M Installation And Maintenance Instruction Download Page 119](http://html1.mh-extra.com/html/bentone/bg-550i-m/bg-550i-m_installation-and-maintenance-instruction_2735590119.webp)
Par
.
no.
Parameter
Num- ber of ele- ments
T
ype
Edit
V
alue range
Min Max
Resolu-
tion
Default setting
Passwor
d
level
148
Default output if communication with building automation
is interrupted
Setting values:
For
modulation operation
the setting range is as follows:
0…19.9 = burner off
20…100 = 20…100% burner rating
For
multistage operation
apply to setting range:
0 = burner OFF, P1, P2, P3
Invalid = no default output predefined by building
automation
Default setting:
Invalid
1
Output
edit / clear
0%
100%
0.1%
undefined
SO (BA)
161
Number of faults
1
Std_u16
read only
0
65535
1
0
Info / Service
162
Operating hours resettable
1
Std_s32
reset
0 h
9999999 h
1 h
0 h
Info / Service
163
Operating hours when unit is live
1
Std_s32
read only
0 h
9999999 h
1 h
0 h
Info / Service
164
Number of startups resettable
1
Std_s32
reset
0
9999999
1
0
Info / Service
166
Total number of startups
1
Std_s32
read only
0
9999999
1
0
Info / Service
167
Fuel volume resettable [m³, l, ft³, gal]
1
Std_s32
reset
0
99999999
1
0
Info / Service
176
Switching back to pilot
switching cycles
1
Std_s32
read only
0
9999999
1
0
Info / Service
190
Postpurging in lockout position
0 = deactivate (no-load position)
1 = active (postpurge position)
When active, the
Alarm in the event of start prevention
function is only possible to a limited extent!
1
Selection
edit
0
1
1
0
SO
191
Function
Switching back to pilot
0 = deactivate
1 = active (low active)
2 = active (high active)
Load controller contacts X5-03 are deactivated when
function is active!
1
Std_u8
edit
0
2
1
0
SO
192
Switching back to pilot
minimum time
1
Time
edit
5 s
120 s
0,2 s
30 s
SO
193
Switching back to pilot
maximum time
1
Time
edit
30 s
108 min.
0,2 s
60 min.
SO
195
Repetition limit heavy oil direct start
1 = no repetition
2...15 = 1...14 number of repetitions
16 = constant repetition
1
Std_u8
edit
1
16
1
3
SO
200
Basic unit
Summary of Contents for BG 550i M
Page 31: ...32 Bentone I I J G G G H 172 615 56 2018 08 10 ...
Page 63: ...63 Bentone 13 2 Wiring diagram 172 615 84 1 2021 05 19 2 ...
Page 64: ...64 Bentone 13 3 Wiring diagram RWF 50 3 172 615 84 1 2021 05 19 3 ...
Page 65: ...65 Bentone 13 4 Wiring diagram RWF 50 2 172 615 84 1 2021 05 19 4 ...
Page 66: ...66 Bentone 13 5 Wiring diagram Jumo 316 172 615 84 1 2021 05 19 5 ...
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com ...