Grade of gas
Excess air flue gases
Max % CO
2
% O
2
% CO
2
Lambda 1,2
Natural gas
3 - 5
≈10
11,9
Propane
3 - 5
≈11,5
13,9
Butane
3 - 5
≈11,5
14,1
Liquefied
petroleum gas
(LPG)
3 - 5
≈11
13,8
5.6 Determining the gas quantity for
the system
The heat values indicated are normal values; the heat value varies according
to the origin of the gas. For more exact information on values, contact the
gas distributor.
Lower heat value Hu at normal state 15°C and 1013.25 mbar
Grade of gas
kWh/Nm
3
MJ/Nm
3
kcal/Nm
3
Natural gas
G20
9,5
34,02
8126
Propane
G25
8,2
29,25
6986
Butane
G31
24,6
88,00
21019
Town gas
G30
32,5
116,09
27728
Biogas
6,0
21,60
5159
172 525 62-1 2021-04-26/3