15.4.1.10
Continuous fan
A burner can be converted into a continuous fan using conversion kit
119 230 01. See the documentation provided with the kit for instructions on
how to perform the conversion.
15.4.1.11
Continuous operation
The LMV37 automatic control unit permits continuous operation of the
burner, provided that the burner’s detector flame is an ionisation detector
flame.
When forced intermittent operation is activated, the unit shuts down for a
moment after 23 hours and 45 min of uninterrupted operation, followed by
an automatic restart.
When forced intermittent operation is inactivated the burner will run
continuously.
Forced intermittent operation is a standard feature.
239 Gas: Forced intermittent operation
0 = inactivate
1 = activated
Factory settings marked with bald text.