Err
or
code
Diagnostic code
Meaning for the LMV37.4... system
Remedy
242 (-14)
Backup – backup made is inconsistent
Backup is faulty and cannot be transferred back
243 (-13)
Backup – data comparison between µCs faulty
Repeat reset and backup
244 (-12)
Backup data are incompatible
Backup data are incompatible with the current software version,
restore not
possible
245 (-11)
Access error to parameter Restore_Complete
Repeat reset and backup
246 (-10)
Restore – timeout when storing in EEPROM
Repeat reset and backup
247 (-9)
Data received are inconsistent
Backup data set invalid, restore not possible
248 (-8)
Restore cannot at present be made
Repeat reset and backup
249 (-7)
Restore – abortion due to unsuitable burner identification
Backup has an unsuitable burner identification and must not be t
ransferred to
the unit
250 (-6)
Backup – CRC of one page is not correct
Backup data set invalid, restore not possible
251 (-5)
Backup – burner identification is not defined
Define burner identification and repeat backup
252 (-4)
After restore, pages still on ABORT
Repeat reset and backup
253 (-3)
Restore cannot at present be made
Repeat reset and backup
254 (-2)
Abortion due to transmission error
Repeat reset and backup
255 (-1)
Abortion due to timeout during restore
Make a reset, check the connections and repeat the backup
146
#
Timeout building automation interface
Refer to User Documentation Modbus (A7541)
1
Modbus timeout
150
#
TÜV test
1 (-1)
Invalid phase
TÜV test may only be started in phase 60 (operation)
2 (-2)
TÜV test default output too low
TÜV test default output must be lower than the lower output limit
3 (-3)
TÜV test default output too high
TÜV test default output must be higher than the upper output lim
it
4 (-4)
Manual abortion
No error: Manual abortion of TÜV test by the user
5 (-5)
TÜV test timeout
No loss of flame after fuel valves have been shut
1. Check for extraneous light
2. Check wiring for short-circuit
3. Check to see if one of the valves is leaking
165
#
Internal error
166
0
Internal error watchdog reset
167
#
Manual locking
Unit has been manually locked (no error)
1
Manual locking by contact
2
Manual locking by AZL2...
3
Manual locking by PC software
8
Manual locking by the AZL2...
Timeout / communication breakdown
During a curve adjustment via the AZL2..., the timeout for menu operation has
elapsed (setting via parameter 127), or communication between
the LMV37.4...
and the AZL2... has broken down
Summary of Contents for BG 550i M
Page 31: ...32 Bentone I I J G G G H 172 615 56 2018 08 10 ...
Page 63: ...63 Bentone 13 2 Wiring diagram 172 615 84 1 2021 05 19 2 ...
Page 64: ...64 Bentone 13 3 Wiring diagram RWF 50 3 172 615 84 1 2021 05 19 3 ...
Page 65: ...65 Bentone 13 4 Wiring diagram RWF 50 2 172 615 84 1 2021 05 19 4 ...
Page 66: ...66 Bentone 13 5 Wiring diagram Jumo 316 172 615 84 1 2021 05 19 5 ...
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com ...