![Bentone BG 550i M Installation And Maintenance Instruction Download Page 94](http://html1.mh-extra.com/html/bentone/bg-550i-m/bg-550i-m_installation-and-maintenance-instruction_2735590094.webp)
94
Bentone
To the next parameter
+
P
V
h
min
s
%
Bi
ld
1
2
7
/0
7
0
7
The minimum capacity is displayed.
If the display shows - - - -, the minimum
capacity has not yet been entered.
The system can be run down to 20%.
You can press
/reset
to go to editing mode, enabling you to
change the minimum capacity.
Adjust the setting downwards or upwards using the buttons
-
+
Press
/reset
to save the setting.
Press
ESC
-
+
to return to parameter level.
The benefit of setting the minimum input power in this way is that at a
later date it is easy to change the input power without having to adjust the
amount of air and gas. The setting curve is therefore adjusted to the lowest
input power that the installation can handle. The desired input power is then
set by entering how much of the minimum power is required.
Completing parameterization of the curve
ESC
-
+
Back to the previous parameter
-
P
V
h
min
s
%
Bi
ld
9
4
/0
7
0
7
When symbol
or
is no longer highlighted, you can press
ESC
a
second time.
Press
ESC
-
+
to exit parameter level.
P
V
h
min
s
%
Bi
ld
1
2
8
/0
7
0
7
The settings for air-fuel ratio control by the LMV37.4... are now completed.
Summary of Contents for BG 550i M
Page 31: ...32 Bentone I I J G G G H 172 615 56 2018 08 10 ...
Page 63: ...63 Bentone 13 2 Wiring diagram 172 615 84 1 2021 05 19 2 ...
Page 64: ...64 Bentone 13 3 Wiring diagram RWF 50 3 172 615 84 1 2021 05 19 3 ...
Page 65: ...65 Bentone 13 4 Wiring diagram RWF 50 2 172 615 84 1 2021 05 19 4 ...
Page 66: ...66 Bentone 13 5 Wiring diagram Jumo 316 172 615 84 1 2021 05 19 5 ...
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com ...