![Bentone BG 550i M Installation And Maintenance Instruction Download Page 116](http://html1.mh-extra.com/html/bentone/bg-550i-m/bg-550i-m_installation-and-maintenance-instruction_2735590116.webp)
116
Bentone
15.9.2 Activation of Manually OFF in operation and
adjustment of output via the display and
operating unit
When the burner is in operation position it can be set to Manually OFF which
means that the load of the burner can be manually set and will not start if the
burner is shut down.
To activate Manually OFF, first run the system to the minimum output limit.
Manual OFF can be activated by pressing
F
for at least 1 second then
LoAd 0.0
appears flashing.
Adjustment of
LoAd
can now manually be done by pressing
F
and
simultaneous pressing
-
or
+
.
The burner will now stay in set input if none of the safety regulators stops the
burner.
To deactivate and to change to automatic operation, press
ESC
-
+
for 3
seconds.
!
Manually OFF must not be used just to put a burner out of operation when doing mounting work, or
when the burner is not ready for operation. The safety notes contained in chapter Safety notes must be
observed!
!
If Manually OFF is activated, it is stored via mains OFF.
On power return, the burner assumes the Manually OFF position (OFF flashing).
!
Please note that the automatic control unit will not exit manual mode by itself. Make sure that the
automatic control unit is reset to automatic mode.
!
The unit can be changed to manual mode without login taking place. If the automatic control unit has
been left in manual mode, no automatic burner control will take place, which in turn means that the
installation is not operating satisfactorily. For this reason, make sure when servcing/troubleshooting that
the automatic control unit is not in manual mode.
Summary of Contents for BG 550i M
Page 31: ...32 Bentone I I J G G G H 172 615 56 2018 08 10 ...
Page 63: ...63 Bentone 13 2 Wiring diagram 172 615 84 1 2021 05 19 2 ...
Page 64: ...64 Bentone 13 3 Wiring diagram RWF 50 3 172 615 84 1 2021 05 19 3 ...
Page 65: ...65 Bentone 13 4 Wiring diagram RWF 50 2 172 615 84 1 2021 05 19 4 ...
Page 66: ...66 Bentone 13 5 Wiring diagram Jumo 316 172 615 84 1 2021 05 19 5 ...
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com ...