84
ATICS-DIO_D00080_03_M_XXEN / 04.2021
Troubleshooting
Fault/message
Description
Action
Functional test
by __ (date)
Reminder for next test
• Schedule appointment for next test.
• Perform test.
Manual mode
Message "Manual mode" although manual
mode has not been enabled
• Check the connections of the digital
input
Phase sequence
This line does not have a right phase
sequence. If the direction of the phase
sequence of line 1 is different from line 2,
it may result in malfunctions or failure on
connected three-phase devices.
• Install line 1 and line 2 in a way that
the direction of the phase sequence
of both lines is clockwise (right).
Error during
changeover process
Occurs when the test set-ups do not supply
sufficient current to switch the coils of the
ATICS®.
• Only use test set-ups that provide
the necessary peak current of 17 A.
8.1.2 Messages with error code or service code
Error code/service
code
Description
Action
1.xx, 4.xx, 9.xx
Fault message from the internal memory
monitoring.
• Contact the Bender service.
3.10
Prewarning
The max. number of
operating hours will be reached in one year.
• For functional safety SIL 2 require-
ments according to IEC 61508-2,
the replacement must be planned.
Alarm can be acknowledged
• (see chapter „Reset menu 3: Change-
3.11
Maximum number of operating hours
exceeded for functional safety according to
IEC 61508-2:2010.
• For functional safety SIL 2 require-
ments according to IEC 61508-2, the
replacement must be carried out.
Alarm can be acknowledged
• (see chapter „Reset menu 3: Change-
3.12
Maximum number of changeovers
exceeded.
• Plan device replacement. Alarm
can be acknowledged (see chapter
„Reset menu 3: Changeover“ on p.
57)
3.13
Changeover due to overcurrent or short
circuit detected. These changeovers reduce
the life of the device. Currents exceeding
130 A or 250 A are considered to be overcur-
rents or short-circuit currents.
• Have qualified personnel assess the
short-circuit load.
Contact the Bender service. Alarm
can be acknowledged (see chapter
„Reset menu 3: Changeover“ on p.
57)
Summary of Contents for ATICS Series
Page 10: ...10 ATICS DIO_D00080_03_M_XXEN 04 2021 Intended use...
Page 12: ...12 ATICS DIO_D00080_03_M_XXEN 04 2021 System description...
Page 17: ...ATICS DIO_D00080_03_M_XXEN 04 2021 17 ATICS DIO...
Page 21: ...ATICS DIO_D00080_03_M_XXEN 04 2021 21 ATICS DIO...
Page 35: ...ATICS DIO_D00080_03_M_XXEN 04 2021 35 ATICS DIO ATICS 4 DIO...
Page 37: ...ATICS DIO_D00080_03_M_XXEN 04 2021 37 ATICS DIO...
Page 38: ...38 ATICS DIO_D00080_03_M_XXEN 04 2021 Mounting and connection ATICS 4 DIO...
Page 39: ...ATICS DIO_D00080_03_M_XXEN 04 2021 39 ATICS DIO...
Page 88: ...88 ATICS DIO_D00080_03_M_XXEN 04 2021 Periodic verification and service...