10. Serviceinterv.
Service interval:
Setting range:
off, 6…48 months
Resolution of setting: 6 months
11. Reminder
Warning time for service interval (d=day):
Setting range:
off, 1…60 days
Resolution of setting: 1 day
12. t (GenStart)
Time delay for changeover to generator (measured from "Voltage line 2 = OK"):
Setting range:
0 s…100 s (only active when System=Line G)
Resolution of settings:
1 s / 5 s
13. t(GenMax)
Maximum generator start time. Monitoring whether the generator starts (time until
"Voltage line 2 = OK").
Setting range:
0 s…100 s (only active when System=Line G)
Resolution of setting:
1 s / 5 s
14. t(Gen.off)
Time delay for turning off the generator after switching back to
the preferred line:
Setting range:
2 s…180 min (only active when System=Line G)
Resolution of setting:
1 s / 5 s / 1 min
7.3.4.2 Settings menu 2: Voltage
In this menu you can make settings for voltage monitoring on line 1 and line 2 individually or together.
Example:
Line 1 is set to "Undervolt: 184 V". If the voltage on line 1 falls below 184 V, the device
displays an alarm message. If the voltage on line 2 is within the set range, a changeover to
line 2 takes place. The ATICS® returns to line 1 if the voltage on line 1 exceeds the pre-set
value (in this case 184 V) plus the set hysteresis.
Selecting a line:
1. Use the " " arrow button to go to the line setting. Press the " " button.
2. Use the arrow buttons to select one line (voltage 1, 2) or both lines (voltage 1…2).
Press the " " button to confirm your selection.
Setting voltage for one line
Setting voltage for both lines
Voltage:
1 . . 2
Exit
1. Undervolt.:
184V
2. Overvoltage:
250V
Voltage:
2
Exit
1. Undervolt.:
184V
2. Overvoltage.
250V
Summary of Contents for ATICS Series
Page 10: ...10 ATICS DIO_D00080_03_M_XXEN 04 2021 Intended use...
Page 12: ...12 ATICS DIO_D00080_03_M_XXEN 04 2021 System description...
Page 17: ...ATICS DIO_D00080_03_M_XXEN 04 2021 17 ATICS DIO...
Page 21: ...ATICS DIO_D00080_03_M_XXEN 04 2021 21 ATICS DIO...
Page 35: ...ATICS DIO_D00080_03_M_XXEN 04 2021 35 ATICS DIO ATICS 4 DIO...
Page 37: ...ATICS DIO_D00080_03_M_XXEN 04 2021 37 ATICS DIO...
Page 38: ...38 ATICS DIO_D00080_03_M_XXEN 04 2021 Mounting and connection ATICS 4 DIO...
Page 39: ...ATICS DIO_D00080_03_M_XXEN 04 2021 39 ATICS DIO...
Page 88: ...88 ATICS DIO_D00080_03_M_XXEN 04 2021 Periodic verification and service...