ATICS-DIO_D00080_03_M_XXEN / 04.2021 53
ATICS-…-DIO
6.2.3.1 Test menu 1: Autom. changeover
Autom. changeover
Test of the changeover function. The device switches to the redundant line.
The changeover period t(1->2) is displayed. After the set time t(test) has
elapsed, the device switches back to the preferred line.
Cancel
Return to test menu
The date of the test is saved in the test logger to send a reminder for the next test once the test interval
has elapsed. The messages from this test are also stored in the history memory.
6.2.3.2 Test menu 2: Manual changeover
Manual changeover
Test of the changeover function. The device switches to the redundant line and
remains in this switch position. The changeover period t(1->2) is displayed. The device does not switch
back to the preferred line until the "RESET" button has been pressed.
Cancel
Return to test menu
The date of the test is saved in the test logger to send a reminder for the next test once the test interval
has elapsed. The messages from this test are also stored in the history memory.
I
r
isk
that the test is accidentally not completed.
If the test menu 3: "Manual changeover" is left after switching over to the redundant line, then the
ATICS® remains in this switch position and in "TEST" mode.
- Wait until "Quit: RESET" appears on the display.
- Press the "RESET" button.
- Check whether the ATICS® has switched to the preferred line.
Autom. changeover
Cancel
Autom. changeover
Test
t (1->2):
457ms
t (Test):
10s
Quit:
RESET
Manual changeover
Cancel
Manual changeover
Test
t (1->2):
346ms
t (Test):
--
Quit:
RESET
Summary of Contents for ATICS Series
Page 10: ...10 ATICS DIO_D00080_03_M_XXEN 04 2021 Intended use...
Page 12: ...12 ATICS DIO_D00080_03_M_XXEN 04 2021 System description...
Page 17: ...ATICS DIO_D00080_03_M_XXEN 04 2021 17 ATICS DIO...
Page 21: ...ATICS DIO_D00080_03_M_XXEN 04 2021 21 ATICS DIO...
Page 35: ...ATICS DIO_D00080_03_M_XXEN 04 2021 35 ATICS DIO ATICS 4 DIO...
Page 37: ...ATICS DIO_D00080_03_M_XXEN 04 2021 37 ATICS DIO...
Page 38: ...38 ATICS DIO_D00080_03_M_XXEN 04 2021 Mounting and connection ATICS 4 DIO...
Page 39: ...ATICS DIO_D00080_03_M_XXEN 04 2021 39 ATICS DIO...
Page 88: ...88 ATICS DIO_D00080_03_M_XXEN 04 2021 Periodic verification and service...