32
ATICS-DIO_D00080_03_M_XXEN / 04.2021
Mounting and connection
ATICS-2-DIO terminals
Legend
Terminal
Description
1, 3
Connection line 1 (input line) L, N
5, 7
Connection line 2 (input line) L, N
4, 6
Connection line 3 (output line) N, L
l, k (grey)
Connection measuring current transformer STW3/STW 4 (T3) for monitoring the load
current downstream the transfer switching device (short-circuit monitoring)
GND, En/Ex
(grey)
Connection must not be used. These terminals are exclusively intended for future
extensions.
IN1/GND, IN1
(grey)
Digital input, configurable, e.g. to monitor the switch position of the transfer switching
and monitoring device
NC, NC (grey)
Not used
24, 34, 44, 21
(white)
3 alarm relays (1 N/O contact each), 21 = common ground for the three alarm relays
IN2, IN3, IN4, IN2-4
GND (white)
3 digital inputs
A, B (black)
BMS bus connection
14, 12, 11 (black)
Alarm relay, configurable function
I
atiCs-4-125a-Dio
and ATICS-4-160A-DIO only: High temperatures may affect the terminals!
The terminals for the connection of line, 1, 2, 3 are designed for the specified rated operational cur-
rent at room temperature. -> Avoid higher temperatures or ensure that the load current is reduced.
I
II
1
3
5
7
2
4
6
8
1L
2N
2L
1N
N
L
l
NC
NC
EN/
EX
IN1/
GND IN1
GND
k
grau
A
NC
11
12
14
NC
NC
B
sch
wa
rz
21
IN3
IN2
44
34
24
IN2-4
GND
IN4
weiß
Summary of Contents for ATICS Series
Page 10: ...10 ATICS DIO_D00080_03_M_XXEN 04 2021 Intended use...
Page 12: ...12 ATICS DIO_D00080_03_M_XXEN 04 2021 System description...
Page 17: ...ATICS DIO_D00080_03_M_XXEN 04 2021 17 ATICS DIO...
Page 21: ...ATICS DIO_D00080_03_M_XXEN 04 2021 21 ATICS DIO...
Page 35: ...ATICS DIO_D00080_03_M_XXEN 04 2021 35 ATICS DIO ATICS 4 DIO...
Page 37: ...ATICS DIO_D00080_03_M_XXEN 04 2021 37 ATICS DIO...
Page 38: ...38 ATICS DIO_D00080_03_M_XXEN 04 2021 Mounting and connection ATICS 4 DIO...
Page 39: ...ATICS DIO_D00080_03_M_XXEN 04 2021 39 ATICS DIO...
Page 88: ...88 ATICS DIO_D00080_03_M_XXEN 04 2021 Periodic verification and service...