ATICS-DIO_D00080_03_M_XXEN / 04.2021 13
ATICS-…-DIO
3
System description
3.1
Properties
3.1.1 Product description
The ATICS® automatic transfer switching devices provide all functions for changeover between two in-
dependent power supplies and for monitoring unearthed power supplies. The integration of both the
electronic system and the switching elements in one flat, compact device reduces space requirements
in the switchgear cabinet, minimises the amount of wiring, and reduces the fault probability. For maxi-
mum reliability, ATICS® was designed in strict accordance with the guidelines for functional safety.
Connectors at all connecting wires, in combination with the optional bypass switch, enable the ATICS®
to be tested or replaced during service works without interruption of the power supply. ATICS® consid-
erably enhances the safety level in industry and other sensitive environments like hospitals.
3.1.2 Changeover
• Automatic changeover to the second (redundant) line on loss of the preferred supply or
when the values are outside the permissible voltage range
• Voltage monitoring line 1/2 (input) and line 3 (output)
• Automatic return to the preferred line on voltage recovery
• Monitoring for short circuits at the output or at the distribution board downstream of the
transfer switching device avoids damaging switching operations
• Manual operation, with optional locking by means of a padlock
3.1.3 Messages
• Status indication of operating, warning and alarm messages via the integrated graphic dis-
play and external indication on MK2430/MK800/TM800 or CP9xx alarm indicator and operator
panels
• Automatic reminder for prescribed tests and service intervals
• History memory for events, messages, tests and parameter changes
• Exchange of information with alarm indicator and operator panels via BMS bus
3.1.4 Other functions
• Automatic monitoring of all programme and data storage as well as essential internal compo-
nents and connecting wires for proper functioning
• 4 programmable relay outputs (alarm relay)
• 4 programmable digital inputs
3.2
Functional safety
Functional safety according to IEC 61508 guarantees safety from risks due to malfunction when used
properly. The ATICS® is suitable for use in safety-related systems according to SIL2. SIL stands for "Safety
Integrity Level".
Summary of Contents for ATICS Series
Page 10: ...10 ATICS DIO_D00080_03_M_XXEN 04 2021 Intended use...
Page 12: ...12 ATICS DIO_D00080_03_M_XXEN 04 2021 System description...
Page 17: ...ATICS DIO_D00080_03_M_XXEN 04 2021 17 ATICS DIO...
Page 21: ...ATICS DIO_D00080_03_M_XXEN 04 2021 21 ATICS DIO...
Page 35: ...ATICS DIO_D00080_03_M_XXEN 04 2021 35 ATICS DIO ATICS 4 DIO...
Page 37: ...ATICS DIO_D00080_03_M_XXEN 04 2021 37 ATICS DIO...
Page 38: ...38 ATICS DIO_D00080_03_M_XXEN 04 2021 Mounting and connection ATICS 4 DIO...
Page 39: ...ATICS DIO_D00080_03_M_XXEN 04 2021 39 ATICS DIO...
Page 88: ...88 ATICS DIO_D00080_03_M_XXEN 04 2021 Periodic verification and service...