ATICS-DIO_D00080_03_M_XXEN / 04.2021 57
ATICS-…-DIO
6.2.4.1 Reset menu 1: Alarm
Delete
Reset alarm and fault messages on the device. The progress of the test is
shown on the display. The RESET is required if one or more alarm-triggering
parameters are not constantly monitored and thus the end of the alarm
condition has not been detected.
Cancel
Return to reset menu
For all pending alarms, the date and time of the reset are entered in the line "End" in the history memo-
ry. The "ALARM" LED goes out. If the fault persists, a new entry is written to the history memory. The
"ALARM" LED remains lit.
6.2.4.2 Reset menu 2: Switch-Back Lock
Delete Disable the switch-back lock of the changeover function. The progress of the test is shown on
the display. The device switches back to the preferred line.
Cancel
Return to reset menu
i
There are different possibilities to disable the switch-back lock via gateway (COM4xx, CP700 etc.):
• Via menu: Select "RESET > Switch-back lock". Requirement: Parameter setting must be possible
(menu "Settings > Interface > Settings > On").
• Via Modbus control commands: Using the command "Changeover to line 1 or line 2".
Testing must be enabled (menu "Settings > Interface > Test > On").
6.2.4.3 Reset menu 3: Changeover
I
C
aution
!
With increasing service life, the probability of component failure increases for every
technical product.
For operation according to IEC 61508-2, additional limit values are monitored (number of switching
cycles, operating time, number of switching cycles in the event of a short circuit). If the set limit va-
lues are exceeded, the device displays a prewarning or an alarm.
The alarm can be "deleted" by increasing the limit values.
To ensure continued operation in accordance with the IEC 61508-2 standard, the device must be re-
placed.
Delete
Cancel
Delete
Delete
Cancel
Delete
Summary of Contents for ATICS Series
Page 10: ...10 ATICS DIO_D00080_03_M_XXEN 04 2021 Intended use...
Page 12: ...12 ATICS DIO_D00080_03_M_XXEN 04 2021 System description...
Page 17: ...ATICS DIO_D00080_03_M_XXEN 04 2021 17 ATICS DIO...
Page 21: ...ATICS DIO_D00080_03_M_XXEN 04 2021 21 ATICS DIO...
Page 35: ...ATICS DIO_D00080_03_M_XXEN 04 2021 35 ATICS DIO ATICS 4 DIO...
Page 37: ...ATICS DIO_D00080_03_M_XXEN 04 2021 37 ATICS DIO...
Page 38: ...38 ATICS DIO_D00080_03_M_XXEN 04 2021 Mounting and connection ATICS 4 DIO...
Page 39: ...ATICS DIO_D00080_03_M_XXEN 04 2021 39 ATICS DIO...
Page 88: ...88 ATICS DIO_D00080_03_M_XXEN 04 2021 Periodic verification and service...