Donut Robot Mark II TS
MN-1013EN
27
To change operator level parameters: (Must be unlocked)
1.
Press the
O
key for less than 1 second
2.
Press the
M
key to move to the next parameter
3.
Press the
U
or
D
to change the parameter
4.
Press the
O
key to return to operator screen
Operator level parameters
Process Value Input Shift
0.0
0.0 °F/°C
ins
This is the offset setting
for calibration
Hysteresis (Heating)
1.0
0.5 °F/°C
hys
.
To change initial level parameters: (Must be unlocked)
1.
Press the
O
key for move than 1 second to adjust intial parameters
2.
Press the
M
key to move to the next parameter
3.
Press the
U
or
D
to change the parameter
4.
Press the
O
key for more than 1 second return to operator screen
Initial level parameters
Input Type
5
8 .
in-t
8:Thermocouple[J] (-
20.0 to 400.0°C or 0.0 to
750.0°F) [
8
]
Temperature Unit
0
1 .
d-u
°F [
f
]
SP Upper Limit
130.0 400.0/200.0 °F/°C
sl-h
.
SP Lower Limit
-20.0
0.0 °F/°C
sl-l
.
Alarm 2 Type
2
0 .
alt2
0:Alarm function OFF
[
0
]
Alarm 3 Type
2
0 .
alt3
0:Alarm function OFF
[
0
]
Alarm 4 Type
2
0 .
alt4
0:Alarm function OFF
[
0
]
To change advanced level parameters: (Must be unlocked)
1.
Unlock the controller
2.
Press the
O
key for more than 1 second to adjust intial parameters
3.
Press the
M
key until you get to parameter
amov
4.
Press the
U
or
D
to change
amov
parameter to -169
Advanced level parameters
Alarm 1 Latch
0
1 .
a1lt
Enabled
[
on
]
PV/SP No. 1 Display Selection
4
1 .
spd1
1:"PV/SP/No display"
[
1
]
PV Decimal Point Display
1
0 .
pVdp
OFF [
off
]
SB-0446 R0
01/19/15