Donut Robot Mark II TS
MKII Temperature Controller Programming procedure
This service bulletin covers the procedure for programing the TJ-0184D-3 or 4 (Omron E5CC-RX3DM-000) temperature
controller used in a Mark II, Mark V or Mark VI.
The TJ-0184D-2 controller comes per-programmed and protected so the operator cannot change the setup parameters.
To change any setting you must first unlock the controller.
Note
: Only the settings that are changed from the Factory settings are listed below.
To unlock the controller:
1.
Press the
O
+
M
keys for more than 3 seconds
2.
Press the
M
key to move to the next parameter
3.
Press the
U
or
D
to change the parameter
oapt
and
icpt
from 2 to 0
4.
Press the
O
+
M
keys for more than 1 second to return to operator screen
Parameter
Factory
default
setting
Present
setting
Unit
Front panel
Explanation of present
setting
Protection parameters
Operation/Adjustment Protect
0
2 .
oapt
2:Display and change of
only "PV" and "PV/SP"
parameters is allowed.
[
2
]
Initial Setting/Communications
Protect
1
2 .
icpt
2:Prohibited [
2
]
To change operator set points: (Must be unlocked to change Alarm Value 1)
1.
Press the
M
key to move to the next parameter
2.
Press the
U
or
D
to change the parameter
3.
Press the
O
key to return to operator screen
Operator set points
Set Point
0.0 375.0/190.0 °F/°C
.
.
Alarm Value 1
0.0
10.0/5.0 °F/°C
al-1
.
SB-0446 R0
01/19/15