4.1 General information
15
4 Assembly and wiring
4.1
General information
Mount the module on a level surface with at least 2 screws.
Use washers for all fastening methods as per DIN 125.
The module has a ground connection with an M4 thread to dissipate
interference currents and for EMC immunity.
Connect the module with a low-impedance connection with the reference
ground.
When using a grounded mounting surface, you can make the
connection directly via the fixing screws; this does not apply for lateral
connection.
In case of a non-grounded mounting surface, or lateral connection,
use a ground strap or a suitable PE conductor. To do this, use an M4
screw to connect the ground strap or the PE line to the ground point
and if possible locate a washer and a toothed lock washer below the
fixing screw.
Fastening method
Screw
Tightening torque
Flat
M4 × 30/35
1.0 Nm
Lateral
M4 × 40/70
1.0 Nm
Table 3:
Fastening methods