The integrated web server
34
6.3 The Configuration page (Config)
Technical manual LioN-Link BusHead EtherNet/IP™
Release 1.1 04/2016
After determining the final configuration, this setting should then be
changed to "Do not accept" in order to detect swapping of I/O modules or
the wiring immediately and check for the correct structure. This setting is
not mandatory, since error-free operation of the system and the
replacement of defective modules is possible in "Accept" mode.
I/O modules
Parameterization of the I/O modules is dependent on the module type.
The "Settings" button is only shown for I/O modules where configurations
can be changed.
NOTE
With the "Accept" setting, the modified actual configuration is adopted as
the new target configuration when the system is restarted. Selecting "Do not
accept" specifies the existing configuration!