6.5 The System page
41
Perform a power on reset of the BusHead by briefly interrupting the power
supply. Before you start the firmware update, make sure that the power
supply will not be interrupted during the update process. The two green
LEDs "US1" and "US2" must light up continuously.
In your browser, open the integrated web server (see chapter
integrated web server” on page 29
Click on the "System" tab, and in the "Firmware update" section select the
file for the firmware update via the "Search" button.
Start the update process by clicking the "Update" button.
When the firmware update has finished loading, the "Reset device to
activate new firmware." message appears. After executing a Power-On
Reset, the new firmware is loaded.
Finally restore the connection to the LioN Link I/O modules, the control
and possibly other EtherNet I/O devices.
NOTE
You must not change the file name!
NOTE
Note that the BusHead does not detect the current LioN Link I/O module
configuration until you have reset the power supply.