Description 

Display 

range 

Explanation 

P0-01 

1st Analog Input Value 

-100 %  .. 100 % 

100% = max input voltage for Analog input1, Terminal 6 

P0-02 

2nd Analog Input Value 

0 to 100 % 

100% = max input voltage for Analog input2, Terminal 10 

P0-03 

Digital Input Status 

00000 to 11111 

One digit per input starting with Digital In1 to the left 

P0-04 

Speed Reference Input 

-P1-01 … P1-01 

Displayed in Hz if P-10 = 0, otherwise displayed in RPM 

P0-05 

Torque Controller Reference 

0 to 500 % 

Displays the set point torque reference input 

P0-07 

Fieldbus Speed Reference 

-P1-01 … P1-01 

Displays set point frequency received from Fieldbus interface 

P0-08 

PID Reference (Setpoint)  

0 to 100 % 

Displays the setpoint input to the PID controller 

P0-09 

PID Feedback Level  

0 to 100 % 

Displays the Feedback input signal to the PID controller  

P0-10 

PID Controller Output  

0 to 100 % 

Displays the output level of the PID controller  

P0-11 

Motor Voltage 

0 … 600V AC 

Value of RMS voltage applied to motor 

P0-12 

Output Torque 

Displays instantaneous output torque level for the motor 

P0-13 

Trip Log 

 

Displays the four latest fault codes 

P0-14 

Motor Magnetising Current (Id) 

Displays motor magnetising current after an auto tune 

P0-15 

Motor Rotor Current (Iq) 

Displays motor rotor current after an auto tune 

P0-16 

DC Bus Voltage Ripple Level 

Displays the level of ripple present on the DC Bus Voltage.  

P0-17 

Motor Stator resistance (Rs) 

Ω 

Displays measured motor stator resistance after an auto tune 

P0-18 

Motor Stator Inductance (Ls) 

Displays measured motor stator inductance after an auto tune 

P0-19 

Motor Rotor Resistance (Rr) 

Ω 

Displays measured motor rotor resistance after an auto tune 

P0-20 

DC Bus Voltage 

0 … 1000V dc 

Internal DC bus voltage 

P0-21 

Internal Temperature 

-20 … 100 °C 

Temperature of heatsink in °C 

P0-25 

Rotor Speed  

Hz / rpm 

In Vector control mode, displays the estimated rotor speed of the motor or 

measured rotor speed with Encoder Feedback 

P0-26 

kWh meter 

0 to 999,9 

When overflow P00-27 increases by 1 and reset to 0. 

P0-27 

MWh meter 

0 to 65535 

Displays the amount of energy consumed by the drive. 

P0-28 

Software Version 

 

I/O-version, I/O Checksum, DSP version, DSP checksum. 

P0-29 

Drive Type 

 

Frame size, Power rating and output phases 

P0-30 

Drive Serial Number 

 

Unique drive serial number. 

P0-31 

Total Run Time 

hours 

Displays the total operating time of the drive. 

P0-35 

Fan Run Time 

0 .. 99999 hours 

Displays total operating time of internal cooling fans. 

P0-36 

DC Bus Voltage at Trip  

V DC 

Values logged before trip with 8 samples total (256 msec). 

P0-37 

DC Bus Voltage Ripple at Trip 

V DC 

Values logged before trip with 8 samples total (20 msec). 

P0-38 

Heatsink Temperature at Trip 

-20 … 100 °C 

Values logged before trip with 8 samples total (30 sec). 

P0-39 

Ambient Temperature at Trip 

°C 

Values logged before trip with 8 samples total (30 sec). 

P0-40 

Motor Current Log at Trip 

Values logged before trip with 8 samples total (256 msec). 

P0-41 

Over Current Fault Counter 

 

Over Current fault counter 

P0-42 

Over Voltage Fault Counter 

 

Over Voltage fault counter 

P0-43 

Under Voltage Fault Counter 

 

Under Voltage fault counter 

P0-44 

Heatsink Over Temperature  

 

Heatsink Over Temperature fault counter 

P0-45 

Brake Chopper Short Circuit  

 

Brake Chopper Short Circuit fault counter 

P0-46 

Ambient Over Temperature  

 

Ambient Over Temperature fault counter 

P0-49 

Modbus RTU  

 

Modbus RTU communication fault counter  

P0-58 

Encoder Feedback Speed Value  

Hz / rpm 

 

P0-60 

Calculated Slip Speed Value (V/F 

Mode Only)  

When slip compensation is enabled using P1-10, the calculated motor slip is 

displayed here. The raw value is displayed 

P0-64 

Switching Frequency 

kHz 

Displays the actual effective Switching frequency 

P0-65 

Drive Life Time 

 

Powered up time, hours, min, and sec 

P0-70 

Option Module ID-code 

 

Identifies Type of Option Module inoption module slot 

P0-71 

Fieldbus module ID 

 

Fieldbus module Identification Code  

P0-74 

L1 – L2 Input Voltage  

Displays the supply voltage measured between L1 and L2 terminals 

P0-75 

L2 – L3 Input Voltage  

Displays the supply voltage measured between L2 and L3 terminals 

P0-76 

L3 – L1 Input Voltage  

Displays the supply voltage measured between L3 and L1 terminals 

P0-77 

Encoder Pulse Count (32bit) 

pulses 

Hi 16-bit and Lo 16-bit 

P0-78 

Test Parameter ¾ 

 

 

P0-79

 

Boot Loader/Motor Control version

 

 

 

P0-80 

User Defined Internal Parameter  

 

Parameter P6-28 decides value to be shown 

 

Summary of Contents for BFI-P2

Page 1: ...and socket connector do not disconnect until 10 minutes have elapsed after turning off the supply Ensure correct earthing connections The earth cable must be sufficient to carry the maximum supply fau...

Page 2: ...VECTOR CONTROL 20 6 1 VECTOR CONTROL 21 6 2 ENCODER 21 6 3 PM MOTOR 22 6 4 PLC 22 6 5 KEYPAD 22 6 6 DRIVE OPERATING DISPLAY OLED KEYPAD IP55 AND IP66 23 6 7 ACCESSING AND CHANGING PARAMETER VALUES OL...

Page 3: ...IP66 Rating Drive BFI P2 IP66 Drive size A Height mm B mm D mm E mm F Depth mm G Width mm H mm I mm J mm Weight kg 1 x 230 V 3 x 230 V 3 x 400 V 0043 0105 0 75 2 2 kW 0043 0105 0 75 2 2 kW 0022 0095...

Page 4: ...W 0043 0105 0 75 2 2kW 0022 0095 0 75 4 0 kW 2 221 207 137 209 5 3 185 110 63 1 8 None 0180 0240 4 0 5 5kW 0140 0240 5 5 11 kW 3 261 246 247 6 205 131 80 3 5 0390 0460 7 5 11 kW 0300 0460 15 22 kW 4 4...

Page 5: ...240 0460 11 22 kW 4 450 428 433 8 252 171 110 8 5 15 12 0610 0720 15 18 5 kW 0610 0900 30 45 kW 5 540 515 520 8 270 235 175 8 5 15 23 0900 1800 22 45 kW 1100 2020 55 110 kW 6 865 830 840 10 330 330 20...

Page 6: ...2x70 240 2 70 100 3900 6 160 3020 308 400 2x185 2x95 302 2x95 100 4800 6 200 3700 522 600 370 2x95 100 3400 2 200 394 500 250 4500 634 800 450 2x150 100 4250 2 250 478 600 NOTE Operation with single p...

Page 7: ...Level Without Derating Derate by Maximum Permissible IP20 IP55 and IP66 1000m 3281ft 1 per 100m 328 ft 4000m 13123 ft Derating for Switching frequency Example of Applying Derating Factors A 4kW IP66 d...

Page 8: ...CY FKKJ EMC or similar Shield of the motor cable should be connected to ground earth in both ends On motor side an EMC gland is to be used Shield of motor cable is to be connected to ground terminal...

Page 9: ...removed if when required OD BR100 BFI is mounted inside an IP20 Size2 and 3 drives and with a resistance of 100 and continuous power of 200 W OD BRES4 BFI is mounted inside IP55 Size4 and 5 drives wit...

Page 10: ...of EMC filter for BFI P2 IP55 and IP66 must be carried out by Beijer Electronics Size 2 and 3 Size 4 Size 5 Size 6A and 6B Disconnect EMC filter by removing the marked screw or screws 4 10IP66 Integra...

Page 11: ...VAC is off This is done by an external 24VDC supply to terminal 1 and 0 VDC to terminal 7 This must be a 24 VDC power supply only used for BFI s and no other units Do not mix external 24 VDC supply wi...

Page 12: ...P1 10 Motor Rated Speed 0 Rpm If not 0 all speed related parameters will be displayed in rpm Setting of rated motor speed enables the slip compensation function Setting of rated motor synchronus speed...

Page 13: ...xed Preset speeds Start in two directions and up to 8 fixed speeds If only 4 fixed speeds are to be used AIN2 terminal 10 can be excluded If only 2 fixed speeds are to be used AIN1 terminal 6 can be e...

Page 14: ...from the motor cable Otherwise an external PTC relay might be needed due to disturbances Para meter Name Default setting Function P2 11 Analog Output 1 Function 8 Digital Output Mode Logic 1 24VDC 0...

Page 15: ...Remote device station Exclusive station 2 P5 01 P5 03 9 6 156 kbs 19 2 625 kbs 38 4 2 5 Mbs 57 6 5 Mbs 115 2 10 Mbs Ethercat ESI_BFI_ECT_V_1_09_2 0190507_XML Set by master Set by master DeviceNet 005...

Page 16: ...decimal places 405 4 05kW 2 Digital Input Status Bit 0 Digital input 1 status Bit 1 Digital input 2 status etc 3 Analog Input 2 Signal Level 0 to 1000 0 to 100 0 4 Drive Heat sink Temperature in C 5 U...

Page 17: ...P1 14 Parameter Access 0 201 Get access to parameter group 5 P5 01 Drive Fieldbus Adress 0 Stationnumber 0 63 First Drive should be stationnumber 1 P5 03 Baud Rate 115 2 9 6 19 2 38 4 57 6 or 115 2 k...

Page 18: ...on included OPT 2 J45SP BFI T Connection of 2 serial cables into one drive RJ45 male to BFI and 2 female RJ45 for network OPT 2 RJTRM BFI RJ45 with a 120 ohm resistor To be put in the last BFI splitte...

Page 19: ...P1 14 must be set to 201 to access all parameters in the drive The BFI Smartstick must also be unlocked to write parameters See manual BFI Smartstick on www beijerelectronics com BFI Smartstick can be...

Page 20: ...Set Up procedure Check System criteria effecting auto tune have not change See step 3 in standard set up procedure If any of these setting have changed then the Auto tune procedure must be repeated To...

Page 21: ...the drive will attempt to ramp and then maintain the motor speed in relation to the reference Available torque on the motor shaft can be limited in parameter P4 07 Maximum motoring Torque limit Motor...

Page 22: ...manent Magnet Motor Control 6 4 PLC BFI Tools is a PC based commissioning and programming software that can be used with all drives in the BFI series With multi drive support and PLC programming possi...

Page 23: ...are open Displayed when the drive power is applied motor stopped Drive operating display showing output information Drive trip display showing trip condition ML on left side of the display indicated...

Page 24: ...r 2s The display shows P Def Drive is returned to factory settings Press the Stop key Note Parameters cannot be defaulted whilst P2 39 1 parameter set locked Parameters can also be put to origin User...

Page 25: ...0 0Hz P1 01 200 0 0 0 P1 01 200 0 0 0 Adjusting individual digits within a parameter value Maximum Speed Limit Maximum Speed Limit 50 0Hz 50 0Hz P1 01 200 0 0 0 P1 01 200 0 0 0 6 11IP20 Changing param...

Page 26: ...drive will decrease speed until is released The rate of deceleration is limited by the setting in P1 04 Press the key The drive will decelerate to rest at the rate set in P1 04 The display will finall...

Page 27: ...d reset to 0 P0 27 MWh meter 0 to 65535 Displays the amount of energy consumed by the drive P0 28 Software Version I O version I O Checksum DSP version DSP checksum P0 29 Drive Type Frame size Power r...

Page 28: ...0 600 0 sec S4 S7 10 0 Seconds Default Setting 0 1 sec Resolution 0 6000 sec Stop Mode Ramping Fast stop Coasting DC brake Zero speed holding time Motor Overload Protection Internal control of output...

Page 29: ...limit specified for the relevant drive Ensure the motor nameplate parameters are correctly in P1 07 P1 08 P1 09 If operating in Vector mode P4 01 0 or 1 also check the motor power factor in P4 05 and...

Page 30: ...tput torque limit has exceeded the drive capacity or trip threshold Reduce the motor load or increase the acceleration time U tor9 25 Output torque too low Minimum torque limit exceeded Active only wh...

Page 31: ...Beijer Electronics Frequency Inverter BFI P2 KI00306B 2020 03 www beijer se www beijer no www beijer dk www beijerelectronics com www beijerelectronics de www beijerelektronik com tr 31 31...

Reviews: