Beijer Electronics Frequency Inverter BFI-P2 

                         

KI00306B           2020-03 

 

 

 

 

www.beijer.se  www.beijer.no  www.beijer.dk

  

www.beijerelectronics.com  www.beijerelectronics.de   www.beijerelektronik.com.tr       

6 (31) 

    

 

4.4  Fuses, cable dimensions and power losses 

200-240V ±10% - 1 Phase Input – 3 Phase Output

 

Output 
Power  

BFI-
P2 
model  

Nominal 
Input 
Current 

Fuse or 
MCB 
(type B) 

Supply 
Cable 
Size,     

A1 

40°C 

Supply 
Cable 
Size,      
E

 3

0°C 

Nominal 
Output 
Current  

Motor 
Cable 
Size,      
E

 3

0°C 

Max 
Motor 
Cable 
Length 

Power 
losses 

 

Recommended 
Brake resistor 

kW  

  

Amps 

Amps 

mm

2

 

mm

2

 

Amps 

mm

2

 

ohm 

0.75 

0043 

8,5 

10 

10,5 

1,5 

4,3 

1,5 

100 

22,5 

100 

1.5 

0070 

15,2 

16 

2,5 

1,5 

7,0 

1,5 

100 

50 

50 

2.2 

0105 

19,5 

25 

2,5 

10,5 

1,5 

100 

66 

35 

380-480V ±10% - 3 Phase Input – 3 Phase Output

 

Output 
Power 
[kW] 

BFI-
P2 
model  

Nominal 
Input 
Current 

Fuse or 
MCB 
(type B) 

Supply 
Cable 
Size, 

A1 

40°C 

Supply 
Cable 
Size,      
E

 3

0°C 

Nominal 
Output 
Current  

Motor 
Cable 
Size,      
E

 3

0°C 

Max 
Motor 
Cable 
Length 

Power 
losses 

 

Recommended  
Brake resistor 

  

  

Amps 

Amps 

mm

2

 

Amps 

Amps 

mm

2

 

ohm 

0.75 

0022 

2,4 

1.5 

1.5 

2.2 

1.5 

100 

15 

400 

1.5 

0041 

5,1 

1.5 

1.5 

4.1 

1.5 

100 

50 

200 

2.2 

0058 

7,5 

10 

1.5 

1.5 

5.8 

1.5 

100 

50 

150 

0095 

11,2 

16 

2.5 

1,5 

9.5 

1.5 

100 

120 

100 

5.5 

0140 

19 

20 

2,5 

14 

1.5 

100 

165 

75 

7.5 

0180 

21 

25 

2,5 

18 

2,5 

100 

225 

50 

11 

0240 

29 

32 

2,5 

24 

100 

330 

40 

15 

0300 

37 

50 

16 

30 

100 

450 

22 

18,5 

0390 

47 

50 

16 

39 

10 

100 

550 

22 

22 

0460 

52 

63 

25 

10 

46 

16 

100 

660 

22 

30 

0610 

64 

80 

35 

16 

61 

16 

100 

900 

12 

37 

0720 

76 

80 

35 

16 

72 

16 

100 

1110 

12 

45 

0900 

92 

100 

70 

25 

90 

35 

100 

1350 

55 

1100 

112 

125 

70 

35 

110 

35 

100 

1650 

75 

1500 

153 

160 

120 

50 

150 

50 

100 

2250 

90 

1800 

184 

200 

150 

95 

180 

95 

100 

2700 

110 

2020 

206 

250 

185 

150 

202 

150 

100 

3300 

132 

2400 

244 

315 

2x150 

2x70 

240 

2*70 

100 

3900 

160 

3020 

308 

400 

2x185 

2x95 

302 

2x95 

100 

4800 

200 

3700 

522 

600 

370 

2x95 

100 

3400 

200* 

394 

500 

250 

4500 

634 

800 

450 

2x150 

100 

4250 

250* 

478 

600 

NOTE 

Operation with single phase supply is possible, with 50% derating of the output current capacity.  
The maximum motor cable length stated applies to using a shielded motor cable. When using an unshielded cable, the maximum 

cable length limit may be increased by 50%. Maximum cable length may be increased by 100% by using an output choke.  
PWM output switching from any inverter when used with a long motor cable length can cause an increase in the voltage at the 
motor terminals, depending on the motor cable length and inductance. The rise time and peak voltage can affect the service life 

of the motor. Beijer recommend using output choke for motor cable lengths of 50m or more to ensure good motor service life.  
For UL compliant installation, use Copper wire with a minimum insulation temperature rating of 70°C, UL Class CC or Class J Fuses  

200* and 250* is with 4% input Line choke.

 

The data above is provided to show typical values. Results measured at the point of installation may 
vary according to the installation site and load conditions Test results are measured under 230- or 
400-Volt RMS AC Supply Voltage, Operating IE2 motor with matching power rating according to 
the drive and Operated at full rated output current capacity. All recommended sizes of cable sizes 
and fuses are recommendations. National laws and recommendations are to be considered. 
Recommended choice of cable sizes and fuses follows DIN VDE 0100 paragraph 430 Appendix, 
motor cable is copper, way of wiring A1 and E is following SS 424 24 24 edition. A1 means cable/ 
conductors in some kind of duct in a maximum temperature of 40°C. E means cable/ conductors 
mounted on a ladder. Calculated at 30°C with 9 or several cables (correction factor 0,78).  

Summary of Contents for BFI-P2

Page 1: ...and socket connector do not disconnect until 10 minutes have elapsed after turning off the supply Ensure correct earthing connections The earth cable must be sufficient to carry the maximum supply fau...

Page 2: ...VECTOR CONTROL 20 6 1 VECTOR CONTROL 21 6 2 ENCODER 21 6 3 PM MOTOR 22 6 4 PLC 22 6 5 KEYPAD 22 6 6 DRIVE OPERATING DISPLAY OLED KEYPAD IP55 AND IP66 23 6 7 ACCESSING AND CHANGING PARAMETER VALUES OL...

Page 3: ...IP66 Rating Drive BFI P2 IP66 Drive size A Height mm B mm D mm E mm F Depth mm G Width mm H mm I mm J mm Weight kg 1 x 230 V 3 x 230 V 3 x 400 V 0043 0105 0 75 2 2 kW 0043 0105 0 75 2 2 kW 0022 0095...

Page 4: ...W 0043 0105 0 75 2 2kW 0022 0095 0 75 4 0 kW 2 221 207 137 209 5 3 185 110 63 1 8 None 0180 0240 4 0 5 5kW 0140 0240 5 5 11 kW 3 261 246 247 6 205 131 80 3 5 0390 0460 7 5 11 kW 0300 0460 15 22 kW 4 4...

Page 5: ...240 0460 11 22 kW 4 450 428 433 8 252 171 110 8 5 15 12 0610 0720 15 18 5 kW 0610 0900 30 45 kW 5 540 515 520 8 270 235 175 8 5 15 23 0900 1800 22 45 kW 1100 2020 55 110 kW 6 865 830 840 10 330 330 20...

Page 6: ...2x70 240 2 70 100 3900 6 160 3020 308 400 2x185 2x95 302 2x95 100 4800 6 200 3700 522 600 370 2x95 100 3400 2 200 394 500 250 4500 634 800 450 2x150 100 4250 2 250 478 600 NOTE Operation with single p...

Page 7: ...Level Without Derating Derate by Maximum Permissible IP20 IP55 and IP66 1000m 3281ft 1 per 100m 328 ft 4000m 13123 ft Derating for Switching frequency Example of Applying Derating Factors A 4kW IP66 d...

Page 8: ...CY FKKJ EMC or similar Shield of the motor cable should be connected to ground earth in both ends On motor side an EMC gland is to be used Shield of motor cable is to be connected to ground terminal...

Page 9: ...removed if when required OD BR100 BFI is mounted inside an IP20 Size2 and 3 drives and with a resistance of 100 and continuous power of 200 W OD BRES4 BFI is mounted inside IP55 Size4 and 5 drives wit...

Page 10: ...of EMC filter for BFI P2 IP55 and IP66 must be carried out by Beijer Electronics Size 2 and 3 Size 4 Size 5 Size 6A and 6B Disconnect EMC filter by removing the marked screw or screws 4 10IP66 Integra...

Page 11: ...VAC is off This is done by an external 24VDC supply to terminal 1 and 0 VDC to terminal 7 This must be a 24 VDC power supply only used for BFI s and no other units Do not mix external 24 VDC supply wi...

Page 12: ...P1 10 Motor Rated Speed 0 Rpm If not 0 all speed related parameters will be displayed in rpm Setting of rated motor speed enables the slip compensation function Setting of rated motor synchronus speed...

Page 13: ...xed Preset speeds Start in two directions and up to 8 fixed speeds If only 4 fixed speeds are to be used AIN2 terminal 10 can be excluded If only 2 fixed speeds are to be used AIN1 terminal 6 can be e...

Page 14: ...from the motor cable Otherwise an external PTC relay might be needed due to disturbances Para meter Name Default setting Function P2 11 Analog Output 1 Function 8 Digital Output Mode Logic 1 24VDC 0...

Page 15: ...Remote device station Exclusive station 2 P5 01 P5 03 9 6 156 kbs 19 2 625 kbs 38 4 2 5 Mbs 57 6 5 Mbs 115 2 10 Mbs Ethercat ESI_BFI_ECT_V_1_09_2 0190507_XML Set by master Set by master DeviceNet 005...

Page 16: ...decimal places 405 4 05kW 2 Digital Input Status Bit 0 Digital input 1 status Bit 1 Digital input 2 status etc 3 Analog Input 2 Signal Level 0 to 1000 0 to 100 0 4 Drive Heat sink Temperature in C 5 U...

Page 17: ...P1 14 Parameter Access 0 201 Get access to parameter group 5 P5 01 Drive Fieldbus Adress 0 Stationnumber 0 63 First Drive should be stationnumber 1 P5 03 Baud Rate 115 2 9 6 19 2 38 4 57 6 or 115 2 k...

Page 18: ...on included OPT 2 J45SP BFI T Connection of 2 serial cables into one drive RJ45 male to BFI and 2 female RJ45 for network OPT 2 RJTRM BFI RJ45 with a 120 ohm resistor To be put in the last BFI splitte...

Page 19: ...P1 14 must be set to 201 to access all parameters in the drive The BFI Smartstick must also be unlocked to write parameters See manual BFI Smartstick on www beijerelectronics com BFI Smartstick can be...

Page 20: ...Set Up procedure Check System criteria effecting auto tune have not change See step 3 in standard set up procedure If any of these setting have changed then the Auto tune procedure must be repeated To...

Page 21: ...the drive will attempt to ramp and then maintain the motor speed in relation to the reference Available torque on the motor shaft can be limited in parameter P4 07 Maximum motoring Torque limit Motor...

Page 22: ...manent Magnet Motor Control 6 4 PLC BFI Tools is a PC based commissioning and programming software that can be used with all drives in the BFI series With multi drive support and PLC programming possi...

Page 23: ...are open Displayed when the drive power is applied motor stopped Drive operating display showing output information Drive trip display showing trip condition ML on left side of the display indicated...

Page 24: ...r 2s The display shows P Def Drive is returned to factory settings Press the Stop key Note Parameters cannot be defaulted whilst P2 39 1 parameter set locked Parameters can also be put to origin User...

Page 25: ...0 0Hz P1 01 200 0 0 0 P1 01 200 0 0 0 Adjusting individual digits within a parameter value Maximum Speed Limit Maximum Speed Limit 50 0Hz 50 0Hz P1 01 200 0 0 0 P1 01 200 0 0 0 6 11IP20 Changing param...

Page 26: ...drive will decrease speed until is released The rate of deceleration is limited by the setting in P1 04 Press the key The drive will decelerate to rest at the rate set in P1 04 The display will finall...

Page 27: ...d reset to 0 P0 27 MWh meter 0 to 65535 Displays the amount of energy consumed by the drive P0 28 Software Version I O version I O Checksum DSP version DSP checksum P0 29 Drive Type Frame size Power r...

Page 28: ...0 600 0 sec S4 S7 10 0 Seconds Default Setting 0 1 sec Resolution 0 6000 sec Stop Mode Ramping Fast stop Coasting DC brake Zero speed holding time Motor Overload Protection Internal control of output...

Page 29: ...limit specified for the relevant drive Ensure the motor nameplate parameters are correctly in P1 07 P1 08 P1 09 If operating in Vector mode P4 01 0 or 1 also check the motor power factor in P4 05 and...

Page 30: ...tput torque limit has exceeded the drive capacity or trip threshold Reduce the motor load or increase the acceleration time U tor9 25 Output torque too low Minimum torque limit exceeded Active only wh...

Page 31: ...Beijer Electronics Frequency Inverter BFI P2 KI00306B 2020 03 www beijer se www beijer no www beijer dk www beijerelectronics com www beijerelectronics de www beijerelektronik com tr 31 31...

Reviews: