Beijer Electronics Frequency Inverter BFI-P2
KI00306B 2020-03
www.beijer.se www.beijer.no www.beijer.dk
www.beijerelectronics.com www.beijerelectronics.de www.beijerelektronik.com.tr
6 (31)
4.4 Fuses, cable dimensions and power losses
200-240V ±10% - 1 Phase Input – 3 Phase Output
Output
Power
BFI-
P2
model
Nominal
Input
Current
Fuse or
MCB
(type B)
Supply
Cable
Size,
A1
40°C
Supply
Cable
Size,
E
3
0°C
Nominal
Output
Current
Motor
Cable
Size,
E
3
0°C
Max
Motor
Cable
Length
Power
losses
Recommended
Brake resistor
kW
Amps
Amps
mm
2
mm
2
Amps
mm
2
m
W
ohm
0.75
0043
8,5
10
10,5
1,5
4,3
1,5
100
22,5
100
1.5
0070
15,2
16
2,5
1,5
7,0
1,5
100
50
50
2.2
0105
19,5
25
6
2,5
10,5
1,5
100
66
35
380-480V ±10% - 3 Phase Input – 3 Phase Output
Output
Power
[kW]
BFI-
P2
model
Nominal
Input
Current
Fuse or
MCB
(type B)
Supply
Cable
Size,
A1
40°C
Supply
Cable
Size,
E
3
0°C
Nominal
Output
Current
Motor
Cable
Size,
E
3
0°C
Max
Motor
Cable
Length
Power
losses
Recommended
Brake resistor
Amps
Amps
mm
2
Amps
Amps
mm
2
m
W
ohm
0.75
0022
2,4
6
1.5
1.5
2.2
1.5
100
15
400
1.5
0041
5,1
6
1.5
1.5
4.1
1.5
100
50
200
2.2
0058
7,5
10
1.5
1.5
5.8
1.5
100
50
150
4
0095
11,2
16
2.5
1,5
9.5
1.5
100
120
100
5.5
0140
19
20
4
2,5
14
1.5
100
165
75
7.5
0180
21
25
4
2,5
18
2,5
100
225
50
11
0240
29
32
6
2,5
24
4
100
330
40
15
0300
37
50
16
6
30
6
100
450
22
18,5
0390
47
50
16
6
39
10
100
550
22
22
0460
52
63
25
10
46
16
100
660
22
30
0610
64
80
35
16
61
16
100
900
12
37
0720
76
80
35
16
72
16
100
1110
12
45
0900
92
100
70
25
90
35
100
1350
6
55
1100
112
125
70
35
110
35
100
1650
6
75
1500
153
160
120
50
150
50
100
2250
6
90
1800
184
200
150
95
180
95
100
2700
6
110
2020
206
250
185
150
202
150
100
3300
6
132
2400
244
315
2x150
2x70
240
2*70
100
3900
6
160
3020
308
400
2x185
2x95
302
2x95
100
4800
6
200
3700
522
600
-
-
370
2x95
100
3400
2
200*
394
500
-
-
250
4500
634
800
-
-
450
2x150
100
4250
2
250*
478
600
-
-
NOTE
Operation with single phase supply is possible, with 50% derating of the output current capacity.
The maximum motor cable length stated applies to using a shielded motor cable. When using an unshielded cable, the maximum
cable length limit may be increased by 50%. Maximum cable length may be increased by 100% by using an output choke.
PWM output switching from any inverter when used with a long motor cable length can cause an increase in the voltage at the
motor terminals, depending on the motor cable length and inductance. The rise time and peak voltage can affect the service life
of the motor. Beijer recommend using output choke for motor cable lengths of 50m or more to ensure good motor service life.
For UL compliant installation, use Copper wire with a minimum insulation temperature rating of 70°C, UL Class CC or Class J Fuses
200* and 250* is with 4% input Line choke.
The data above is provided to show typical values. Results measured at the point of installation may
vary according to the installation site and load conditions Test results are measured under 230- or
400-Volt RMS AC Supply Voltage, Operating IE2 motor with matching power rating according to
the drive and Operated at full rated output current capacity. All recommended sizes of cable sizes
and fuses are recommendations. National laws and recommendations are to be considered.
Recommended choice of cable sizes and fuses follows DIN VDE 0100 paragraph 430 Appendix,
motor cable is copper, way of wiring A1 and E is following SS 424 24 24 edition. A1 means cable/
conductors in some kind of duct in a maximum temperature of 40°C. E means cable/ conductors
mounted on a ladder. Calculated at 30°C with 9 or several cables (correction factor 0,78).