4.7  Safe Torque Off, STO 

BFI-P2 has two digital inputs for Safe Torque Off. These two inputs must be correct 
connected otherwise the Drive will not run and

Inhibit



will be shown on the display. If 

safety is not to be used terminal 12 must be connected to terminal 1 and terminal 13 
connected to terminal 7. More about safety inputs can be read in User Manual BFI-P2.

   

 

4.8  AC-Flux braking and brake transistor and external brake resistor 

If a larger amount of regenerate power is being produced than BFI can handle at stop function AC 
Flux Braking can be used. Means that motor is being over excitated during stop and used as brake 
resistor. Note that heat of motor will increase and it only works during deceleration. Put parameter 
P1-05=4 to activate AC Flux braking. 
If AC Flux braking is not enough BFI has a dynamic brake transistor and an optional external 
braking resistor can be connected to +DC and BR when required. The DC-, DC+ and BR+ 
connections are blanked off by plastic tabs when sent from the factory.  The plastic tabs can 
be removed if/when required. 
OD-BR100-BFI is mounted inside an IP20 Size2 and 3 drives and with a resistance of 100 Ω 
and continuous power of 200 W. OD-BRES4-BFI is mounted inside IP55 Size4 and 5 drives 
with a resistance of 33 Ω and continuous power of 500 W. Resistance must never be lower 
than minimum allowed resistance. Software protection against brake resistor and cable 
overload is carried out within the drive.  
For correct protection:  

o

 

The brake transistor is enabled by putting P1-05=2 

o

 

Enter the resistance of the brake resistor in P6-19 (Ohms) 

o

 

Enter the average (not peak) power of the brake resistor in P6-20 (kW) 

Drive model      

Minimum 

Permissible 

resistance 

[ohm] 

Brakeresistor to be used 

Voltage 

[VAC] 

BFI-P2 

Name 

Power resistor [kW] 

Resistans 

[ohm] 

Average 

Peak for 

0,125 sec 

1-fas  

230  

0043 [0,75kW] -
0105 [2,2kW] 

75 

OD-BR100-BFI or 

BSD600R75-4 

0,2 
0,6 

12          

100 

75 

3-fas 

400 

VAC 

0022 [0,75 kW] -
0095 [4,0 kW] 

100 

OD-BR100-BFI or 

2 pieces of BSD300R82-4 in serial 

0,2 
0,6 

12 

100 
164 

0140 [5,5 kW] - 
0240 [11 kW] 

70 

BSD600R75-4 or  

 2 pieces of BSD-600R140-4 in parallel 

0,6 
1,2 


75 
70 

0300 [15kW] - 
0460 [22kW] 

26 

OD-BRES4-BFI (For IP55 drives) or             

2 pieces of BSD-2000R13-4 in serial 

0,5 
4,0 

33 
26 

0610 [30 kW] - 
0720 [37 kW] 

 

OD-BRES4-BFI (For IP55 drives) or              

BSD-2000R13-4  

0,5 
2,0 

33 
13 

0900 [45 kW] - 
3020 [160 kW] 

 

Contact Beijer Electronics for design of brake resistor 

3700[200 kW] - 
4500 [250 kW] 

Wires should be 
protected 
against short 
circuits as 
shown above 

Summary of Contents for BFI-P2

Page 1: ...and socket connector do not disconnect until 10 minutes have elapsed after turning off the supply Ensure correct earthing connections The earth cable must be sufficient to carry the maximum supply fau...

Page 2: ...VECTOR CONTROL 20 6 1 VECTOR CONTROL 21 6 2 ENCODER 21 6 3 PM MOTOR 22 6 4 PLC 22 6 5 KEYPAD 22 6 6 DRIVE OPERATING DISPLAY OLED KEYPAD IP55 AND IP66 23 6 7 ACCESSING AND CHANGING PARAMETER VALUES OL...

Page 3: ...IP66 Rating Drive BFI P2 IP66 Drive size A Height mm B mm D mm E mm F Depth mm G Width mm H mm I mm J mm Weight kg 1 x 230 V 3 x 230 V 3 x 400 V 0043 0105 0 75 2 2 kW 0043 0105 0 75 2 2 kW 0022 0095...

Page 4: ...W 0043 0105 0 75 2 2kW 0022 0095 0 75 4 0 kW 2 221 207 137 209 5 3 185 110 63 1 8 None 0180 0240 4 0 5 5kW 0140 0240 5 5 11 kW 3 261 246 247 6 205 131 80 3 5 0390 0460 7 5 11 kW 0300 0460 15 22 kW 4 4...

Page 5: ...240 0460 11 22 kW 4 450 428 433 8 252 171 110 8 5 15 12 0610 0720 15 18 5 kW 0610 0900 30 45 kW 5 540 515 520 8 270 235 175 8 5 15 23 0900 1800 22 45 kW 1100 2020 55 110 kW 6 865 830 840 10 330 330 20...

Page 6: ...2x70 240 2 70 100 3900 6 160 3020 308 400 2x185 2x95 302 2x95 100 4800 6 200 3700 522 600 370 2x95 100 3400 2 200 394 500 250 4500 634 800 450 2x150 100 4250 2 250 478 600 NOTE Operation with single p...

Page 7: ...Level Without Derating Derate by Maximum Permissible IP20 IP55 and IP66 1000m 3281ft 1 per 100m 328 ft 4000m 13123 ft Derating for Switching frequency Example of Applying Derating Factors A 4kW IP66 d...

Page 8: ...CY FKKJ EMC or similar Shield of the motor cable should be connected to ground earth in both ends On motor side an EMC gland is to be used Shield of motor cable is to be connected to ground terminal...

Page 9: ...removed if when required OD BR100 BFI is mounted inside an IP20 Size2 and 3 drives and with a resistance of 100 and continuous power of 200 W OD BRES4 BFI is mounted inside IP55 Size4 and 5 drives wit...

Page 10: ...of EMC filter for BFI P2 IP55 and IP66 must be carried out by Beijer Electronics Size 2 and 3 Size 4 Size 5 Size 6A and 6B Disconnect EMC filter by removing the marked screw or screws 4 10IP66 Integra...

Page 11: ...VAC is off This is done by an external 24VDC supply to terminal 1 and 0 VDC to terminal 7 This must be a 24 VDC power supply only used for BFI s and no other units Do not mix external 24 VDC supply wi...

Page 12: ...P1 10 Motor Rated Speed 0 Rpm If not 0 all speed related parameters will be displayed in rpm Setting of rated motor speed enables the slip compensation function Setting of rated motor synchronus speed...

Page 13: ...xed Preset speeds Start in two directions and up to 8 fixed speeds If only 4 fixed speeds are to be used AIN2 terminal 10 can be excluded If only 2 fixed speeds are to be used AIN1 terminal 6 can be e...

Page 14: ...from the motor cable Otherwise an external PTC relay might be needed due to disturbances Para meter Name Default setting Function P2 11 Analog Output 1 Function 8 Digital Output Mode Logic 1 24VDC 0...

Page 15: ...Remote device station Exclusive station 2 P5 01 P5 03 9 6 156 kbs 19 2 625 kbs 38 4 2 5 Mbs 57 6 5 Mbs 115 2 10 Mbs Ethercat ESI_BFI_ECT_V_1_09_2 0190507_XML Set by master Set by master DeviceNet 005...

Page 16: ...decimal places 405 4 05kW 2 Digital Input Status Bit 0 Digital input 1 status Bit 1 Digital input 2 status etc 3 Analog Input 2 Signal Level 0 to 1000 0 to 100 0 4 Drive Heat sink Temperature in C 5 U...

Page 17: ...P1 14 Parameter Access 0 201 Get access to parameter group 5 P5 01 Drive Fieldbus Adress 0 Stationnumber 0 63 First Drive should be stationnumber 1 P5 03 Baud Rate 115 2 9 6 19 2 38 4 57 6 or 115 2 k...

Page 18: ...on included OPT 2 J45SP BFI T Connection of 2 serial cables into one drive RJ45 male to BFI and 2 female RJ45 for network OPT 2 RJTRM BFI RJ45 with a 120 ohm resistor To be put in the last BFI splitte...

Page 19: ...P1 14 must be set to 201 to access all parameters in the drive The BFI Smartstick must also be unlocked to write parameters See manual BFI Smartstick on www beijerelectronics com BFI Smartstick can be...

Page 20: ...Set Up procedure Check System criteria effecting auto tune have not change See step 3 in standard set up procedure If any of these setting have changed then the Auto tune procedure must be repeated To...

Page 21: ...the drive will attempt to ramp and then maintain the motor speed in relation to the reference Available torque on the motor shaft can be limited in parameter P4 07 Maximum motoring Torque limit Motor...

Page 22: ...manent Magnet Motor Control 6 4 PLC BFI Tools is a PC based commissioning and programming software that can be used with all drives in the BFI series With multi drive support and PLC programming possi...

Page 23: ...are open Displayed when the drive power is applied motor stopped Drive operating display showing output information Drive trip display showing trip condition ML on left side of the display indicated...

Page 24: ...r 2s The display shows P Def Drive is returned to factory settings Press the Stop key Note Parameters cannot be defaulted whilst P2 39 1 parameter set locked Parameters can also be put to origin User...

Page 25: ...0 0Hz P1 01 200 0 0 0 P1 01 200 0 0 0 Adjusting individual digits within a parameter value Maximum Speed Limit Maximum Speed Limit 50 0Hz 50 0Hz P1 01 200 0 0 0 P1 01 200 0 0 0 6 11IP20 Changing param...

Page 26: ...drive will decrease speed until is released The rate of deceleration is limited by the setting in P1 04 Press the key The drive will decelerate to rest at the rate set in P1 04 The display will finall...

Page 27: ...d reset to 0 P0 27 MWh meter 0 to 65535 Displays the amount of energy consumed by the drive P0 28 Software Version I O version I O Checksum DSP version DSP checksum P0 29 Drive Type Frame size Power r...

Page 28: ...0 600 0 sec S4 S7 10 0 Seconds Default Setting 0 1 sec Resolution 0 6000 sec Stop Mode Ramping Fast stop Coasting DC brake Zero speed holding time Motor Overload Protection Internal control of output...

Page 29: ...limit specified for the relevant drive Ensure the motor nameplate parameters are correctly in P1 07 P1 08 P1 09 If operating in Vector mode P4 01 0 or 1 also check the motor power factor in P4 05 and...

Page 30: ...tput torque limit has exceeded the drive capacity or trip threshold Reduce the motor load or increase the acceleration time U tor9 25 Output torque too low Minimum torque limit exceeded Active only wh...

Page 31: ...Beijer Electronics Frequency Inverter BFI P2 KI00306B 2020 03 www beijer se www beijer no www beijer dk www beijerelectronics com www beijerelectronics de www beijerelektronik com tr 31 31...

Reviews: