background image

 

Beijer Electronics Frequency Inverter BFI-P2 

                         

KI00306B           2020-03 

 

 

 

 

www.beijer.se  www.beijer.no  www.beijer.dk

  

www.beijerelectronics.com  www.beijerelectronics.de   www.beijerelektronik.com.tr       

4 (31) 

    

 

IP66 drives are fitted with 3 knockout holes for cable inlet and outlet. If more than 3 cables are to 
enter the drive it is possible to have two or more cables going through one gland, this to ensure 
IP66.   
Holes and recommended glands are listed in table below. The motor cable does not have to be 
attached to the drive with an EMC-gland.   

 
 

 

 

4.2  Physical dimension IP20 

 
 
 
 
 
 
 
 
 
 

 

 

BFI-P2-IP20 

Drive 

size 

Height 

[mm]

 

[mm]

 

[mm]

 

[mm]

 

E  

[mm]

 

F

 

Depth 

[mm]

 

Width 

[mm]

 

[mm]

 

Weight   

[kg]

 

1 x 230 V  3 x 230 V 

3 x 400 V 

0043 - 0105          
[0,75-2,2kW] 

0043 - 0105          
[0,75- 2,2kW] 

0022 - 0095                
[0,75 - 4,0 kW] 

221 

207  137 

209 

5.3 

185 

110 

63 

1,8 

None 

0180- 0240          
[4,0- 5,5kW] 

0140 – 0240       
[5,5 - 11 kW] 

261 

246 

247 

205 

131 

80 

3,5 

0390 – 0460                 
[7,5 - 11 kW] 

0300 – 0460                 
[15 - 22 kW] 

418 

 

400 

 

240 

160 

125 

9,2 

0610 – 0720                 
[15 - 18 kW] 

0610 – 0720                 
[30 - 37 kW] 

486 

 

460 

 

260 

222 

175 

18 

0900 – 1100                 
[22 - 30 kW] 

0900 – 1100                 
[45 - 55 kW] 

6A 

614 

 

578 

 

320 

286 

200 

32 

1500 – 1800                 
[37 - 55 kW] 

1500 – 2020                 
[75 - 90 kW] 

6B 

726 

 

680 

 

320 

330 

225 

43 

None 

3700 – 4500                 
[200 - 250 kW] 

995 

 

 

 

 

480 

482 

 

128 

NOTE 

Mounting bolts  

Frame Size 2-3: M4                  Frame Size 4-5 and 6A: M8 
Frame Size 6B: M10                 Frame Size 8: M12 

Control Terminal, Required Torque 

All Frame sizes: 0.5 Nm.  

Power Terminal, Required Torque 

Frame Size 2-3:    1 Nm             Frame Size 4:       2 Nm       
Frame Size 5:       4 Nm             Frame Size 6A:  12 Nm           
Frame Size 6B:  15 Nm 

Cable Gland, IP66 Hole Size & recommended glands

 

Frame size 

Hole sizes 

Gland PG 

Size 2 

1x22mm & 2x28 mm 

1xPG13,5 & 2xPG21 

Size 3 

1x22mm & 2x28 mm 

1xPG13,5 & 2xPG21 

Summary of Contents for BFI-P2

Page 1: ...and socket connector do not disconnect until 10 minutes have elapsed after turning off the supply Ensure correct earthing connections The earth cable must be sufficient to carry the maximum supply fau...

Page 2: ...VECTOR CONTROL 20 6 1 VECTOR CONTROL 21 6 2 ENCODER 21 6 3 PM MOTOR 22 6 4 PLC 22 6 5 KEYPAD 22 6 6 DRIVE OPERATING DISPLAY OLED KEYPAD IP55 AND IP66 23 6 7 ACCESSING AND CHANGING PARAMETER VALUES OL...

Page 3: ...IP66 Rating Drive BFI P2 IP66 Drive size A Height mm B mm D mm E mm F Depth mm G Width mm H mm I mm J mm Weight kg 1 x 230 V 3 x 230 V 3 x 400 V 0043 0105 0 75 2 2 kW 0043 0105 0 75 2 2 kW 0022 0095...

Page 4: ...W 0043 0105 0 75 2 2kW 0022 0095 0 75 4 0 kW 2 221 207 137 209 5 3 185 110 63 1 8 None 0180 0240 4 0 5 5kW 0140 0240 5 5 11 kW 3 261 246 247 6 205 131 80 3 5 0390 0460 7 5 11 kW 0300 0460 15 22 kW 4 4...

Page 5: ...240 0460 11 22 kW 4 450 428 433 8 252 171 110 8 5 15 12 0610 0720 15 18 5 kW 0610 0900 30 45 kW 5 540 515 520 8 270 235 175 8 5 15 23 0900 1800 22 45 kW 1100 2020 55 110 kW 6 865 830 840 10 330 330 20...

Page 6: ...2x70 240 2 70 100 3900 6 160 3020 308 400 2x185 2x95 302 2x95 100 4800 6 200 3700 522 600 370 2x95 100 3400 2 200 394 500 250 4500 634 800 450 2x150 100 4250 2 250 478 600 NOTE Operation with single p...

Page 7: ...Level Without Derating Derate by Maximum Permissible IP20 IP55 and IP66 1000m 3281ft 1 per 100m 328 ft 4000m 13123 ft Derating for Switching frequency Example of Applying Derating Factors A 4kW IP66 d...

Page 8: ...CY FKKJ EMC or similar Shield of the motor cable should be connected to ground earth in both ends On motor side an EMC gland is to be used Shield of motor cable is to be connected to ground terminal...

Page 9: ...removed if when required OD BR100 BFI is mounted inside an IP20 Size2 and 3 drives and with a resistance of 100 and continuous power of 200 W OD BRES4 BFI is mounted inside IP55 Size4 and 5 drives wit...

Page 10: ...of EMC filter for BFI P2 IP55 and IP66 must be carried out by Beijer Electronics Size 2 and 3 Size 4 Size 5 Size 6A and 6B Disconnect EMC filter by removing the marked screw or screws 4 10IP66 Integra...

Page 11: ...VAC is off This is done by an external 24VDC supply to terminal 1 and 0 VDC to terminal 7 This must be a 24 VDC power supply only used for BFI s and no other units Do not mix external 24 VDC supply wi...

Page 12: ...P1 10 Motor Rated Speed 0 Rpm If not 0 all speed related parameters will be displayed in rpm Setting of rated motor speed enables the slip compensation function Setting of rated motor synchronus speed...

Page 13: ...xed Preset speeds Start in two directions and up to 8 fixed speeds If only 4 fixed speeds are to be used AIN2 terminal 10 can be excluded If only 2 fixed speeds are to be used AIN1 terminal 6 can be e...

Page 14: ...from the motor cable Otherwise an external PTC relay might be needed due to disturbances Para meter Name Default setting Function P2 11 Analog Output 1 Function 8 Digital Output Mode Logic 1 24VDC 0...

Page 15: ...Remote device station Exclusive station 2 P5 01 P5 03 9 6 156 kbs 19 2 625 kbs 38 4 2 5 Mbs 57 6 5 Mbs 115 2 10 Mbs Ethercat ESI_BFI_ECT_V_1_09_2 0190507_XML Set by master Set by master DeviceNet 005...

Page 16: ...decimal places 405 4 05kW 2 Digital Input Status Bit 0 Digital input 1 status Bit 1 Digital input 2 status etc 3 Analog Input 2 Signal Level 0 to 1000 0 to 100 0 4 Drive Heat sink Temperature in C 5 U...

Page 17: ...P1 14 Parameter Access 0 201 Get access to parameter group 5 P5 01 Drive Fieldbus Adress 0 Stationnumber 0 63 First Drive should be stationnumber 1 P5 03 Baud Rate 115 2 9 6 19 2 38 4 57 6 or 115 2 k...

Page 18: ...on included OPT 2 J45SP BFI T Connection of 2 serial cables into one drive RJ45 male to BFI and 2 female RJ45 for network OPT 2 RJTRM BFI RJ45 with a 120 ohm resistor To be put in the last BFI splitte...

Page 19: ...P1 14 must be set to 201 to access all parameters in the drive The BFI Smartstick must also be unlocked to write parameters See manual BFI Smartstick on www beijerelectronics com BFI Smartstick can be...

Page 20: ...Set Up procedure Check System criteria effecting auto tune have not change See step 3 in standard set up procedure If any of these setting have changed then the Auto tune procedure must be repeated To...

Page 21: ...the drive will attempt to ramp and then maintain the motor speed in relation to the reference Available torque on the motor shaft can be limited in parameter P4 07 Maximum motoring Torque limit Motor...

Page 22: ...manent Magnet Motor Control 6 4 PLC BFI Tools is a PC based commissioning and programming software that can be used with all drives in the BFI series With multi drive support and PLC programming possi...

Page 23: ...are open Displayed when the drive power is applied motor stopped Drive operating display showing output information Drive trip display showing trip condition ML on left side of the display indicated...

Page 24: ...r 2s The display shows P Def Drive is returned to factory settings Press the Stop key Note Parameters cannot be defaulted whilst P2 39 1 parameter set locked Parameters can also be put to origin User...

Page 25: ...0 0Hz P1 01 200 0 0 0 P1 01 200 0 0 0 Adjusting individual digits within a parameter value Maximum Speed Limit Maximum Speed Limit 50 0Hz 50 0Hz P1 01 200 0 0 0 P1 01 200 0 0 0 6 11IP20 Changing param...

Page 26: ...drive will decrease speed until is released The rate of deceleration is limited by the setting in P1 04 Press the key The drive will decelerate to rest at the rate set in P1 04 The display will finall...

Page 27: ...d reset to 0 P0 27 MWh meter 0 to 65535 Displays the amount of energy consumed by the drive P0 28 Software Version I O version I O Checksum DSP version DSP checksum P0 29 Drive Type Frame size Power r...

Page 28: ...0 600 0 sec S4 S7 10 0 Seconds Default Setting 0 1 sec Resolution 0 6000 sec Stop Mode Ramping Fast stop Coasting DC brake Zero speed holding time Motor Overload Protection Internal control of output...

Page 29: ...limit specified for the relevant drive Ensure the motor nameplate parameters are correctly in P1 07 P1 08 P1 09 If operating in Vector mode P4 01 0 or 1 also check the motor power factor in P4 05 and...

Page 30: ...tput torque limit has exceeded the drive capacity or trip threshold Reduce the motor load or increase the acceleration time U tor9 25 Output torque too low Minimum torque limit exceeded Active only wh...

Page 31: ...Beijer Electronics Frequency Inverter BFI P2 KI00306B 2020 03 www beijer se www beijer no www beijer dk www beijerelectronics com www beijerelectronics de www beijerelektronik com tr 31 31...

Reviews: