Fault Code  No.  OLED Message 

Description 

Corrective Action 

E-trip 

11  External trip 

Digital Input 
External trip 

E-trip requested on control input terminals. Either P1-13 has wrong setting 
or the connected motor thermistor is too hot. 

SC-trp 

12  Optibus fault 

Communications 
Fault 

Communications lost with PC or remote keypad. Check the cables. 

FLt-dc

13  Excessive DC ripple 

Excessive DC Ripple 
on Internal DC bus 

The DC Bus Ripple Voltage level can be displayed in P0-16.  
A historical log is stored at 20ms  intervals prior to a trip in P0-37. 
Check all three supply phases are present and within the 3% supply voltage 
level imbalance tolerance. Reduce the motor load. 

P-LOSS

14  Input phase loss 

Input phase missing 
trip 

One input phase has been disconnected or lost. 

h O-I

15  Instant over current 

Instantaneous over 
current.  

Overcurrent on motor side. Refer to fault 0-I. 

Th-FlT

16  Thermistor Fault 

Faulty thermistor on 
heat-sink. 

Refer to your Beijer office. 

dAtA F

17 

I/O processor data 
error 

Internal memory 
fault. 

Parameters not saved, factory defaults are reloaded. 

4-20 F 

18 

4-20mA signal out of 
range 

4-20mA Signal Lost 

Reference signal on Analog Input 1 or 2 has dropped below 3mA. Check 
the signal source and wiring to the drive terminals. 

dAtA-E 

19  M/C processor error 

Internal memory 
fault. 

Parameters not saved, factory defaults are reloaded. 

U-dEF

20 

User Parameter 
Default 

User Parameter 
Defaults 

User Parameter default has been loaded. Press the Stop key.  

F-Ptc 

21  Motor PTC overheat  Motor PTC  

The connected motor PTC device has caused the drive to trip. 

FAN-F 

22  Cooling Fan Fault 

Cooling Fan Fault 

Check and if necessary, replace the drive internal cooling fan 

O-hEAt 

23 

Ambient 
Temperature High 

Ambient 
Temperature too 
High 

Measured temperature around the drive is above the operating limit. 
Ensure the drive internal cooling fan is operating, cooling airflow path to 
and from the drive is not restricted. Increase the cooling airflow to the 
drive 
Reduce the effective switching frequency or reduce the load on the motor. 

O-tor9

 

24  Exceed max torque 

Maximum torque 
limit exceeded 

The output torque limit has exceeded the drive capacity or trip threshold 
Reduce the motor load or increase the acceleration time. 

U-tor9

 

25 

Output torque too 
low 

Minimum torque 
limit exceeded 

A

ctive only when hoist brake control is enabled P2-18 = 8. The torque 

developed prior to releasing the motor holding brake is below the preset 
threshold. Contact your Beijer Electronics for further information about 
BFI-P2 in hoist applications. 

OUt-F

26  Drive Output Fault 

Drive output fault 

Contact Beijer Electronics. 

Sto-F

29  STO Error Input 2  

STO circuit error  

Internal STO circuit Error. Contact Beijer Electronics. 

Enc-01 

30  Encoder Fault 

Encoder fault 

Encoder communication /data loss 

SP-Err

 

31  Speed Error 

 

Speed Error. The error between the measured encoder feedback speed  
or the estimated rotor speed is greater than the preset limit allowed. 

Enc-03

32 

Encoder Fault 

Encoder Feedback 
Fault 

Incorrect Encoder PPR count set in parameters 

Enc-04

33 

Encoder Channel A Fault 

Enc-05

34 

Encoder Channel B Fault 

Enc-06

35 

Encoder Channels A & B Fault 

AtF-01

40  Autotune fail 1 

Autotune Failed, 
Ensure the motor is 
correctly connected 
and free from faults 

Measured motor stator resistance varies between phases. Check the 
windings for correct resistance and balance. 

AtF-02

41  Autotune fail 2 

Measured motor stator resistance is too large.  

Check that the power 
rating corresponds to 
the power rating of the 
connected drive. 

AtF-03

42  Autotune fail 3 

Measured motor inductance is too low.  

AtF-04

43  Autotune fail 4 

Measured motor inductance is too large.  

AtF-05

44  Autotune fail 5 

Measured motor parameters are not convergent 

Ph-SE9 

45  Input phase 

Input phase sequence 
incorrect 

Applies to Frame Size 8 drives only, indicates that the incoming power 
supply phase sequence is incorrect. Any 2 phases may be swapped. 

Pr-Lo

 

49  Output Phase Loss  

Output Phase Loss  

One of the motor output phases is not connected to the drive.  

SC-F01

 

50  Modbus Comms fault  Modbus comms fault 

A valid Modbus telegram has not been received within the watchdog time 
limit in P5-05. Check the network master operating and cabling. 

SC-F02

 

51 

CanOpen Comms 
fault 

CanOpen Comms 
fault 

A valid CanOpen telegram has not been received within the watchdog time 
limit in P5-06. Check the network master operating and cabling. 

SC-F03

 

52  Option Module Fault 

Communication 
Module Fault 

Check that communications I/O- module is correctly inserted. 

SC-F04

53  IO Card Comms fault  IO card comms trip 

Check that I/O- module is correctly inserted. 

 

Summary of Contents for BFI-P2

Page 1: ...and socket connector do not disconnect until 10 minutes have elapsed after turning off the supply Ensure correct earthing connections The earth cable must be sufficient to carry the maximum supply fau...

Page 2: ...VECTOR CONTROL 20 6 1 VECTOR CONTROL 21 6 2 ENCODER 21 6 3 PM MOTOR 22 6 4 PLC 22 6 5 KEYPAD 22 6 6 DRIVE OPERATING DISPLAY OLED KEYPAD IP55 AND IP66 23 6 7 ACCESSING AND CHANGING PARAMETER VALUES OL...

Page 3: ...IP66 Rating Drive BFI P2 IP66 Drive size A Height mm B mm D mm E mm F Depth mm G Width mm H mm I mm J mm Weight kg 1 x 230 V 3 x 230 V 3 x 400 V 0043 0105 0 75 2 2 kW 0043 0105 0 75 2 2 kW 0022 0095...

Page 4: ...W 0043 0105 0 75 2 2kW 0022 0095 0 75 4 0 kW 2 221 207 137 209 5 3 185 110 63 1 8 None 0180 0240 4 0 5 5kW 0140 0240 5 5 11 kW 3 261 246 247 6 205 131 80 3 5 0390 0460 7 5 11 kW 0300 0460 15 22 kW 4 4...

Page 5: ...240 0460 11 22 kW 4 450 428 433 8 252 171 110 8 5 15 12 0610 0720 15 18 5 kW 0610 0900 30 45 kW 5 540 515 520 8 270 235 175 8 5 15 23 0900 1800 22 45 kW 1100 2020 55 110 kW 6 865 830 840 10 330 330 20...

Page 6: ...2x70 240 2 70 100 3900 6 160 3020 308 400 2x185 2x95 302 2x95 100 4800 6 200 3700 522 600 370 2x95 100 3400 2 200 394 500 250 4500 634 800 450 2x150 100 4250 2 250 478 600 NOTE Operation with single p...

Page 7: ...Level Without Derating Derate by Maximum Permissible IP20 IP55 and IP66 1000m 3281ft 1 per 100m 328 ft 4000m 13123 ft Derating for Switching frequency Example of Applying Derating Factors A 4kW IP66 d...

Page 8: ...CY FKKJ EMC or similar Shield of the motor cable should be connected to ground earth in both ends On motor side an EMC gland is to be used Shield of motor cable is to be connected to ground terminal...

Page 9: ...removed if when required OD BR100 BFI is mounted inside an IP20 Size2 and 3 drives and with a resistance of 100 and continuous power of 200 W OD BRES4 BFI is mounted inside IP55 Size4 and 5 drives wit...

Page 10: ...of EMC filter for BFI P2 IP55 and IP66 must be carried out by Beijer Electronics Size 2 and 3 Size 4 Size 5 Size 6A and 6B Disconnect EMC filter by removing the marked screw or screws 4 10IP66 Integra...

Page 11: ...VAC is off This is done by an external 24VDC supply to terminal 1 and 0 VDC to terminal 7 This must be a 24 VDC power supply only used for BFI s and no other units Do not mix external 24 VDC supply wi...

Page 12: ...P1 10 Motor Rated Speed 0 Rpm If not 0 all speed related parameters will be displayed in rpm Setting of rated motor speed enables the slip compensation function Setting of rated motor synchronus speed...

Page 13: ...xed Preset speeds Start in two directions and up to 8 fixed speeds If only 4 fixed speeds are to be used AIN2 terminal 10 can be excluded If only 2 fixed speeds are to be used AIN1 terminal 6 can be e...

Page 14: ...from the motor cable Otherwise an external PTC relay might be needed due to disturbances Para meter Name Default setting Function P2 11 Analog Output 1 Function 8 Digital Output Mode Logic 1 24VDC 0...

Page 15: ...Remote device station Exclusive station 2 P5 01 P5 03 9 6 156 kbs 19 2 625 kbs 38 4 2 5 Mbs 57 6 5 Mbs 115 2 10 Mbs Ethercat ESI_BFI_ECT_V_1_09_2 0190507_XML Set by master Set by master DeviceNet 005...

Page 16: ...decimal places 405 4 05kW 2 Digital Input Status Bit 0 Digital input 1 status Bit 1 Digital input 2 status etc 3 Analog Input 2 Signal Level 0 to 1000 0 to 100 0 4 Drive Heat sink Temperature in C 5 U...

Page 17: ...P1 14 Parameter Access 0 201 Get access to parameter group 5 P5 01 Drive Fieldbus Adress 0 Stationnumber 0 63 First Drive should be stationnumber 1 P5 03 Baud Rate 115 2 9 6 19 2 38 4 57 6 or 115 2 k...

Page 18: ...on included OPT 2 J45SP BFI T Connection of 2 serial cables into one drive RJ45 male to BFI and 2 female RJ45 for network OPT 2 RJTRM BFI RJ45 with a 120 ohm resistor To be put in the last BFI splitte...

Page 19: ...P1 14 must be set to 201 to access all parameters in the drive The BFI Smartstick must also be unlocked to write parameters See manual BFI Smartstick on www beijerelectronics com BFI Smartstick can be...

Page 20: ...Set Up procedure Check System criteria effecting auto tune have not change See step 3 in standard set up procedure If any of these setting have changed then the Auto tune procedure must be repeated To...

Page 21: ...the drive will attempt to ramp and then maintain the motor speed in relation to the reference Available torque on the motor shaft can be limited in parameter P4 07 Maximum motoring Torque limit Motor...

Page 22: ...manent Magnet Motor Control 6 4 PLC BFI Tools is a PC based commissioning and programming software that can be used with all drives in the BFI series With multi drive support and PLC programming possi...

Page 23: ...are open Displayed when the drive power is applied motor stopped Drive operating display showing output information Drive trip display showing trip condition ML on left side of the display indicated...

Page 24: ...r 2s The display shows P Def Drive is returned to factory settings Press the Stop key Note Parameters cannot be defaulted whilst P2 39 1 parameter set locked Parameters can also be put to origin User...

Page 25: ...0 0Hz P1 01 200 0 0 0 P1 01 200 0 0 0 Adjusting individual digits within a parameter value Maximum Speed Limit Maximum Speed Limit 50 0Hz 50 0Hz P1 01 200 0 0 0 P1 01 200 0 0 0 6 11IP20 Changing param...

Page 26: ...drive will decrease speed until is released The rate of deceleration is limited by the setting in P1 04 Press the key The drive will decelerate to rest at the rate set in P1 04 The display will finall...

Page 27: ...d reset to 0 P0 27 MWh meter 0 to 65535 Displays the amount of energy consumed by the drive P0 28 Software Version I O version I O Checksum DSP version DSP checksum P0 29 Drive Type Frame size Power r...

Page 28: ...0 600 0 sec S4 S7 10 0 Seconds Default Setting 0 1 sec Resolution 0 6000 sec Stop Mode Ramping Fast stop Coasting DC brake Zero speed holding time Motor Overload Protection Internal control of output...

Page 29: ...limit specified for the relevant drive Ensure the motor nameplate parameters are correctly in P1 07 P1 08 P1 09 If operating in Vector mode P4 01 0 or 1 also check the motor power factor in P4 05 and...

Page 30: ...tput torque limit has exceeded the drive capacity or trip threshold Reduce the motor load or increase the acceleration time U tor9 25 Output torque too low Minimum torque limit exceeded Active only wh...

Page 31: ...Beijer Electronics Frequency Inverter BFI P2 KI00306B 2020 03 www beijer se www beijer no www beijer dk www beijerelectronics com www beijerelectronics de www beijerelektronik com tr 31 31...

Reviews: