2–10
M-0420 Instruction Book
M-0420
52
G
SYSTEM
52
G
SYSTEM
M-0420
Protection Applications — Phase-to-Phase Faults
Protective
Device Function
Offline
(Synchronizing)
On-Line
50
51
VR
46
67 *
Applicable Protection
Applicable Protection
Applicable Protection
Applicable Protection
Not Applicable
Not Applicable
Protection Applications — Phase-to-Phase Faults
Protective
Device Function
Offline
(Synchronizing)
On-Line
50
51
VR
46
67 *
Applicable Protection
Applicable Protection
Not Applicable
Applicable Protection
(MSA must be set towards
generator.)
CTs on Neutral Side
CTs on Line Side
Not Applicable
Not Applicable
■
NOTE: The 67 phase directional overcurrent function is optional. Using the 67 function for protec-
tion against inadvertent energizing is applicable to both CT positions.
Table 2-1
Current Transformer Placement Considerations
for Generator Phase-to-Phase Fault Protection