M-0420 Instruction Book
5–26
Figure 5-17
Configure Relays VT Fuse-Loss Blocking (Page 3 of 3)
EXIT
EXIT
EXIT
EXIT
ENTER
ENTER
ENTER
ENTER
ENTER
Rotate knob to make selection
Rotate knob to make selection
ENTER
Rotate knob to enable or disable blocking
Rotate knob to enable or disable blocking
Rotate knob to enable or disable blocking
Rotate knob to enable or disable blocking
SELECT
FUNCTION
ENTER
SETPOINT
CONFIGURE RELAYS
setpts stat CONFIG
➞
➞
SELECT
FUNCTION
ENTER
SETPOINT
CONFIGURE V.T. FUSE LOSS
trip FUSE
➞
➞
INTERNAL FUSE LOSS LOGIC
disable ENABLE
SELECT
FUNCTION
ENTER
SETPOINT
BLOCK PHASE UNDERVOLTAGE
disable ENABLE
SELECT
FUNCTION
ENTER
SETPOINT
BLOCK REVERSE POWER
DISABLE enable
SELECT
FUNCTION
ENTER
SETPOINT
BLOCK TIME OVERCURRENT
disable ENABLE
SELECT
FUNCTION
ENTER
SETPOINT
BLOCK TIME OVERCURRENT
disable ENABLE
SELECT
FUNCTION
ENTER
SETPOINT
ENTER
Rotate knob to enable or disable blocking
EXIT
EXIT
Summary of Contents for M-0420
Page 56: ...M 0420 Instruction Book 3 4 This Page Intentionally Left Blank ...
Page 92: ...M 0420 Instruction Book 5 28 This Page Left Intentionally Blank ...
Page 156: ...A 8 M 0420 Instruction Book This Page Intentionally Left Blank ...
Page 160: ...B 4 M 0420 Instruction Book This Page Intentionally Left Blank ...
Page 164: ...C 4 M 0420 Instruction Book This Page Intentionally Left Blank ...
Page 166: ...D 2 M 0420 Instruction Book This Page Intentionally Left Blank ...
Page 174: ...E 8 M 0420 Instruction Book This Page Intentionally Left Blank ...