Test Procedures – 7
7–1
7
Test Procedures
7.1
Introduction ................................................................................. 7–1
7.2
Unit Setup ................................................................................... 7–1
7.3
Equipment Required ................................................................... 7–2
7.4
Test and Equipment Setup ........................................................ 7–2
7.5
Diagnostic Test Procedures ...................................................... 7–5
7.6
Self-Calibration Procedure ....................................................... 7–43
7.1
Introduction
This chapter presents step-by-step test procedures
for each relay function as well as the diagnostic
mode procedures and the self-calibration procedure.
(The diagnostic mode procedures provide a means
to check the basic functionality of the relay,
including inputs, outputs, the alphanumeric display,
LEDs, buttons, and the COM ports.) Refer to
Figure 6-5 for the external connections diagram.
These tests are based on the three-phase
line-to-neutral configuration, with DIP switches 4
and 5 OFF (up).
7.2
Unit Setup
No calibration is needed since the unit is cali-
brated and fully tested at the factory. If calibra-
tion is necessary because of a component
replacement, follow the self-calibration procedure
detailed at the end of this chapter. These test
procedures are based on the prerequisite that
the functions are enabled and have initial set-
tings as shown in Table 7-1, Initial Settings, the
default, as-shipped configuration. (Functions with
two available setpoints have only setpoint #1
enabled.)
Before beginning these test procedures, examine
the DIP switch settings by going to the SETUP
UNIT menu and selecting DIP SWITCH SETTINGS.
If switches 4 and 5 are shown to be ON (down),
remove the unit from its case and reset them to
OFF. The applied test voltages and the M-0420
responses defined below are valid
only for the
three-phase line-to-neutral configuration. If the unit
is intended for line-to-line service, reset the DIP
switches after completing the tests.
Summary of Contents for M-0420
Page 56: ...M 0420 Instruction Book 3 4 This Page Intentionally Left Blank ...
Page 92: ...M 0420 Instruction Book 5 28 This Page Left Intentionally Blank ...
Page 156: ...A 8 M 0420 Instruction Book This Page Intentionally Left Blank ...
Page 160: ...B 4 M 0420 Instruction Book This Page Intentionally Left Blank ...
Page 164: ...C 4 M 0420 Instruction Book This Page Intentionally Left Blank ...
Page 166: ...D 2 M 0420 Instruction Book This Page Intentionally Left Blank ...
Page 174: ...E 8 M 0420 Instruction Book This Page Intentionally Left Blank ...