Test Procedures – 7
7–41
Time Delay Accuracy Test
TEST SETTINGS:
Reverse Power
Flow Magnitude
–3.0 pu
Time Delay
30 Cycles
13. Press ENTER. The SELECT FUNCTION LED
should turn on and the unit should display
VOLTAGE RELAY
VOLT freq curr powr
C
14. Turn the knob clockwise until the unit displays
POWER RELAY
volt freq curr POWR
C
15. Press ENTER until the unit displays
FORWARD POWER SETPOINTS
FORWARD reverse
16. Turn the knob clockwise until the unit displays
REVERSE POWER SETPOINTS
forward REVERSE
17. Press ENTER until the unit displays
DELAY REVERSE POWER
1 Cycle
18. Turn the knob clockwise until the unit displays
DELAY REVERSE POWER
30 Cycles
19. Press ENTER once and then EXIT until the
unit displays
BECKWITH ELECTRIC CO.
M-0420
20. Increase the input current to 16.00 A and
start timing. The unit should trip after 30
cycles time delay.
21. The 32 DIRECTIONAL OVERPOWER LED
should turn on and the unit should rotate
displays
-TRGT- 06/22/93 10:19:12
Trip# = 32
-TRGT- 06/22/93 10:19:12
REVERSE OVERPOWER
22. Set the input current to 0.00 A.
23. Press TARGET RESET/LAMP TEST. The
32 DIRECTIONAL OVERPOWER LED should
turn off. The unit should display
BECKWITH ELECTRIC CO.
M-0420
—END—
32R
DIRECTIONAL POWER, REVERSE POWER, 3-PHASE (CONT.)
Summary of Contents for M-0420
Page 56: ...M 0420 Instruction Book 3 4 This Page Intentionally Left Blank ...
Page 92: ...M 0420 Instruction Book 5 28 This Page Left Intentionally Blank ...
Page 156: ...A 8 M 0420 Instruction Book This Page Intentionally Left Blank ...
Page 160: ...B 4 M 0420 Instruction Book This Page Intentionally Left Blank ...
Page 164: ...C 4 M 0420 Instruction Book This Page Intentionally Left Blank ...
Page 166: ...D 2 M 0420 Instruction Book This Page Intentionally Left Blank ...
Page 174: ...E 8 M 0420 Instruction Book This Page Intentionally Left Blank ...