Configuration
TF6120
50
Version: 1.1
Settings in the OPC server
An ADS communication partner is always specified by two parameters: These are what is known as the
"AdsAmsNetId" (e.g. 1.2.3.4.5.6) and the "PortId" (e.g. 801 for the first PLC run-time system).
If ADS is to be used to exchange data with, for example, the first PLC run-time system on another PC, then
the AdsAmsNetId of the target PC, and "801" as the PortId, must be entered in the OPC server under
"Device settings".
Please Note
If possible, the option of using the "
" protocol should be selected for performance
reasons.
4.1.7.3
Netzwerk via DCOM
If you need to allow data exchange between an OPC client and the TwinCAT OPC server over a network via
DCOM, this DCOM access type must be configured beforehand.
The following steps describe the necessary settings for the PC on which the TwinCAT OPC server is
installed.
Prerequisites
It is assumed that all the PCs which are to participate via DCOM in an OPC client/server connection are
already set up for network operation (i.e. they have configured network cards running the TCP/IP protocol).
Step 1
Click on "Start"->"Run…" and enter "DCOMcnfg", then select the dialog "Default Settings".
• Activate "Enable Distributed COM on this computer"
• For "Default Authentication Level" select "None"
• For "Default Impersonation Level" select "Anonymous
Step 2
Select the dialog "Applications" and then the entry „TwinCAT OPC Server DA". Double-click this entry.